Plan Review Notes
Plan Review Notes For Permit 15060554
Permit Number 15060554
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-26 09:00:221) SUBMIT ALL DRAWINGS RELATED TO THIS PORTION OF THE
 PROJECT.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT.0142-M-ADF-09 REFERS TO SHT. M-ADF-31 FOR
 INFORMATION ON THE PROPANE TANK/PIPING. SUBMIT THIS
 DRAWING FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) SUBMIT COMPLETE PLANS FOR THE LP TANK & PIPING
 SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SHT.0766-M-STD-09 - DETAIL # 1542102 - THE WYE SHALL
 BE INSTALLED IN THE DIRECTION OF FLOE. REVISE THE
 DETAIL. 2010 FPC SEC. 706.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR