2015-12-07 13:33:14PAGE (FILE) 0479-E-GEN-02.PDF - CONNECTED LOAD AND
 DEMAND LOAD APPEAR TO EXCEED BUS RATING AND 80% OF
 DEMAND (CONTINUOUS) LOAD. PLEASE EXPLAIN
 BUS IS RATED 2000A. CONNECTED LOAD IS 3100 AND DEMAND
 LOAD LOAD IS 1700, GREATER THAN 80%. IS BUS RATED FOR
 CONTINUOUS DUTY?
 IDENTIFY ZONES THAT WILL NEED TO BE DELINEATED FOR
 HAZARDOUS (ELECTRICAL) ZONE OR CLASS AND DIVISION WITH
 THE SPECIFIC HAZARD (METHANE, CHLORINE, ETC.)