| 2015-12-07 13:33:14 | PAGE (FILE) 0479-E-GEN-02.PDF - CONNECTED LOAD AND | | | DEMAND LOAD APPEAR TO EXCEED BUS RATING AND 80% OF | | | DEMAND (CONTINUOUS) LOAD. PLEASE EXPLAIN | | | BUS IS RATED 2000A. CONNECTED LOAD IS 3100 AND DEMAND | | | LOAD LOAD IS 1700, GREATER THAN 80%. IS BUS RATED FOR | | | CONTINUOUS DUTY? | | | IDENTIFY ZONES THAT WILL NEED TO BE DELINEATED FOR | | | HAZARDOUS (ELECTRICAL) ZONE OR CLASS AND DIVISION WITH | | | THE SPECIFIC HAZARD (METHANE, CHLORINE, ETC.) |
|