Plan Review Notes
Plan Review Notes For Permit 15060552
Permit Number 15060552
Review Stop P
Sequence Number 2
Notes
Date Text
2015-10-24 08:21:071) SHT. 0388- A - ADF - 10 - FBC 2010 SEC.1503.4.2.1
 OVERFLOW SCUPPERS - OVERFLOW SCUPPERS SHALL BE LOCATED
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS
 PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR
 WALL AND PARAPET SCUPPERS. NOTE # 2 STATES THE OVERFLOW
 SCUPPER WILL BE 3 INCHES ABOVE THE PRIMARY SCUPPER.
 INCLUDE IN THE NOTE THAT THE OVERFLOW SCUPPER SHALL BE
 NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE
 FINISHED ROOF SURFACE.THIS IS THE LANGUAGE IN THE CODE.
 NOTE #2 STATES "3 INCHES ABOVE THE PRIMARY SCUPPER".
 THIS COULD POSSIBLY BE MISINTERPRETED AS MEANING THE
 TOP OF THE SCUPPER.
 2) PREVIOUS COMMENT #11 - SEPARATE FACILITIES FOR MALES
 & FEMALES - IN ORDER TO REQUEST RELIEF FROM A SECTION
 /REQUIREMENT OF THE PLUMBING CODE IT SHALL BE REQUESTED
 IN WRITING TO THE PLUMBING CODE OFFICIAL ON THE
 REQUESTING PARTY'S LETTERHEAD ( TWO COPIES, IF AN
 ARCHITECT/ENGINEER THE LETTER SHALL BE SIGNED AND
 SEALED ) STATING THE CODE SECTION FROM WHICH THE RELIEF
 IS BEING REQUESTED AND THE JUSTIFICATION FOR SUCH
 RELIEF.
 3) PREVIOUS COMMENT # 10 - INDICATE THE DISTANCE (
 LINEAL FEET) AND THE LOCATION OF THE BUILDINGS WITH THE
 SERVICE SINK ON THE CIVIL DRAWING 0013 - C- GEN - 01 .
 PLEASE PROVIDE A WRITTEN REQUEST AS ABOVE FOR RELIEF
 FROM THE PLUMBING CODE REQUIREMENT FOR THE MOP SINK.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  