| 2015-10-24 08:21:07 | 1) SHT. 0388- A - ADF - 10 - FBC 2010 SEC.1503.4.2.1 |
| | OVERFLOW SCUPPERS - OVERFLOW SCUPPERS SHALL BE LOCATED |
| | NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE |
| | FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS |
| | PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR |
| | WALL AND PARAPET SCUPPERS. NOTE # 2 STATES THE OVERFLOW |
| | SCUPPER WILL BE 3 INCHES ABOVE THE PRIMARY SCUPPER. |
| | INCLUDE IN THE NOTE THAT THE OVERFLOW SCUPPER SHALL BE |
| | NO LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE |
| | FINISHED ROOF SURFACE.THIS IS THE LANGUAGE IN THE CODE. |
| | NOTE #2 STATES "3 INCHES ABOVE THE PRIMARY SCUPPER". |
| | THIS COULD POSSIBLY BE MISINTERPRETED AS MEANING THE |
| | TOP OF THE SCUPPER. |
| | 2) PREVIOUS COMMENT #11 - SEPARATE FACILITIES FOR MALES |
| | & FEMALES - IN ORDER TO REQUEST RELIEF FROM A SECTION |
| | /REQUIREMENT OF THE PLUMBING CODE IT SHALL BE REQUESTED |
| | IN WRITING TO THE PLUMBING CODE OFFICIAL ON THE |
| | REQUESTING PARTY'S LETTERHEAD ( TWO COPIES, IF AN |
| | ARCHITECT/ENGINEER THE LETTER SHALL BE SIGNED AND |
| | SEALED ) STATING THE CODE SECTION FROM WHICH THE RELIEF |
| | IS BEING REQUESTED AND THE JUSTIFICATION FOR SUCH |
| | RELIEF. |
| | 3) PREVIOUS COMMENT # 10 - INDICATE THE DISTANCE ( |
| | LINEAL FEET) AND THE LOCATION OF THE BUILDINGS WITH THE |
| | SERVICE SINK ON THE CIVIL DRAWING 0013 - C- GEN - 01 . |
| | PLEASE PROVIDE A WRITTEN REQUEST AS ABOVE FOR RELIEF |
| | FROM THE PLUMBING CODE REQUIREMENT FOR THE MOP SINK. |
| | |
| | |