| Date |
Text |
| 2015-10-20 07:51:59 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15060552 |
| | 10/20/15 |
| | |
| | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE |
| | ENERGY CALCULATIONS. THE SUBMITTED RESPONSE NARRATIVE |
| | IS INDICATING PLAN ROOM 301 IS A CONDITIONED, OCCUPIED |
| | SPACE AND THEREFORE MUST MEET COMPLIANCE. |
| | 2) AS PREVIOUSLY REQUESTED PROVIDE AC EQUIPMENT |
| | SCHEDULES ON THE PLANS. THE NARRATIVE INDICATES THE |
| | SCHEDULES ARE ON SHEETS 0713-H-SCHD-01 AND |
| | 0714-H-SCHD-02 HOWEVER THESE SHEETS HAVE NOT BEEN |
| | UPLOADED FOR REVIEW. |
| | 3) AS PREVIOUSLY REQUESTED PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS ON THE PLAN. THE NARRATIVE IS INDICATING |
| | SOME OF THE VENTILATION SCHEDULES ARE FOUND ON SHEET |
| | 0714- H-SCH-02 WHICH HAS NOT BEEN UPLOADED. |
| | 4) AS PREVIOUSLY REQUESTED PROVIDE THE SEQUENCE OF |
| | OPERATION FOR THE AC SYSTEMS. THE NARRATIVE STATES THE |
| | INFORMATION CAN BE FOUND IN SECTIONS OF THE PROJECT |
| | SPECIFICATIONS BOOK. PLEASE NOTE A SPECIFICATIONS BOOK |
| | FOR THIS PROJECT IS NOT UPLOADED FOR REVIEW, AND |
| | TYPICALLY REVIEWS ARE DONE ON PLANS, NOT SPEC BOOKS. |
| | PLEASE PROVIDE THE REQUESTED COMPLIANCE DATA ON THE |
| | PLANS. |
| | 5) AS PREVIOUSLY REQUESTED PROVIDE AN AIR DISTRIBUTION |
| | SCHEDULE. THE NARRATIVE STATES THE SCHEDULE CAN BE |
| | FOUND ON SHEET 0714-H-SCHD-02 WHICH IS NOT UPLOADED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |