| 2015-10-20 10:31:49 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060552 DIGESTER ELECTRIC BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. OCT. 20/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID. |
| | |
| | 1-5) COMPLIED. |
| | |
| | |
| | |
| | 6)2ND REQUEST. PAGE 0294-S-ADF-28: |
| | 6A) NOTES PRECAST PRESTRESSED ELEMENTS SHALL BE |
| | DESIGNED FOR THE FOLLOWING: |
| | 1NOTE( E ) WIND LOADS PER CODE. ?PROVIDE THE DESIGN |
| | CRITERIA, 180 VULT, EXPOSURE C, MEAN ROOF HEIGHT 18 FT. |
| | BUILD RISK CAT. III. |
| | |
| | 6B) NOTE 1( F ) EQUIPMENT LOADS. NOT GIVEN . |
| | |
| | 6C) ROOF PRESSURES SUBMITTED DO NOT STATE IF THEY ARE |
| | VULT OR VASD. PRESSURES ARE LOW CONSIDERING THE WIND |
| | DESIGN CRITERIA OF DESIGN CRITERIA, 180 VULT, EXPOSURE |
| | C, MEAN ROOF HEIGHT 18 FT. BUILD RISK CAT. III. TO BE |
| | TAKEN AT 10 SQURE FEET FOR FASTENERS. |
| | |
| | 6D) SHEET 0365-A-GEN-02 COMPONENTS AND CLADDING. |
| | PRESSURES ARE LOW FOR DOORS. WHERE DO YOU FIND |
| | PRESSURES FOR WINDOWS AND WALL LOUVERS. |
| | |
| | 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS, |
| | EXHAUST FANS, RTU'S |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) COMPLIED. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 0365-A-GEN-02 DOOR SCHED. |
| | 0380-A-ADF-02 ELEC. LIFE SAFETY |
| | 0384-A-ADF-06 FLOOR PLAN |
| | 0388-A-ADF10 ROOF PLAN |
| | 0392-A-ADF-14 ELEVATIONS |
| | 0393-A-ADF-15 WALL SEC/ DETAILS |
| | |
| | 0293-S-ADF-27 FOUNDATION |
| | 0294-S-ADF-28 ROOF PLAN |
| | 0295-S-ADF-29 SECTION |
| | 0296-S-ADF-30 DETAILS |
| | 0297-S-ADF-31 SCHEDULES |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |