Plan Review Notes For Permit 15060552
Permit Number 15060552
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-22 04:03:121) SUBMIT ROOF DRAINAGE CALCULATIONS FOR THIS
 STRUCTURE. THE SIZE OF SCUPPERS SHALL COMPLY W/ 2010
 FBC-PLUMBING SEC.1106.7 AND TABLE 1106.7. INCLUDE 1/2
 THE AREA OF ANY VERTICAL WALLS THAT DIVERT RAINWATER TO
 THE ROOF IN THE CALCULATIONS FOR THE ROOF DRAINAGE.
 2) SHT. 0791 - H-STD-01 - DETAIL - SHOW THE SIZE OF THE
 CONDENSATE LINE DISCHARGING TO THE DRYWELL.
 3) IDENTIFY THE SPECIFIC YARD PIPING DRAWINGS FOR THE
 CONTINUATION OF THE WATER AND SEWER LINES. WPB AMEND.
 TO FBC SEC. 107.2.1.
 4) SHT.0723-P-ADF-07 - THE VENT SHALL BE NOT LESS 1/2
 THE SIZE OF THE DRAIN SERVED PER 2010 FBC-PLUMBING,
 SEC. 916.1. THE MINIMUM VENT SIZE SHALL BE 2".
 5) SHUTOFF VALVES ARE REQUIRED ON THE
 FIXTURES.FBC-PLUMBING SEC.606.2.
 6) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE PER 2010 FBC-ACCESSIBILITY
 SEC. 609.4.
 7) SHT. A-ADF-06 - THE ENLARGED TOILET ROOM PLAN - SHOW
 THE CLEAR INSIDE LENGTH AND WIDTH DIMENSIONS FOR THE
 TOILET ROOM.
 8) THE LAVATORY APPEARS TO BE ENCROACHING INTO THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET. THIS IS NOT
 ALLOWED PER FBC-ACCESSIBILITY SEC.604.3.
 9) IF THE LEADING EDGE OF THE "HI" SIDE DRINKING
 FOUNTAIN IS MORE THAN 27 INCHES ABOVE THE FINISH FLOOR
 IN CAN ONLY PROJECT INTO THE CIRCULATION PATH 4 INCHES
 PER 2010 FBC-ACCESSIBILITY SEC.307.2. A SKIRT MAY BE
 REQUIRED TO BE PLACED ON THE UNIT TO MEET COMPLIANCE.
 10) A SERVICE SINK IS REQUIRED FOR THIS OCCUPANCY PER
 TABLE 403.1.
 11) TABLE 403.1 OF 2010 FBC- PLUMBING REQUIRES SEPARATE
 FACILITIES FOR MALES & FEMALES FOR THIS OCCUPANCY. YOU
 MAY REQUEST RELIEF FROM THIS REQUIREMENT TO THE
 PLUMBING OFFICIAL BY WRITTEN REQUEST.
 12) THE OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN
 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS PER 2010 FBC SEC.1503.4.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  