| 2015-07-22 04:03:12 | 1) SUBMIT ROOF DRAINAGE CALCULATIONS FOR THIS |
| | STRUCTURE. THE SIZE OF SCUPPERS SHALL COMPLY W/ 2010 |
| | FBC-PLUMBING SEC.1106.7 AND TABLE 1106.7. INCLUDE 1/2 |
| | THE AREA OF ANY VERTICAL WALLS THAT DIVERT RAINWATER TO |
| | THE ROOF IN THE CALCULATIONS FOR THE ROOF DRAINAGE. |
| | 2) SHT. 0791 - H-STD-01 - DETAIL - SHOW THE SIZE OF THE |
| | CONDENSATE LINE DISCHARGING TO THE DRYWELL. |
| | 3) IDENTIFY THE SPECIFIC YARD PIPING DRAWINGS FOR THE |
| | CONTINUATION OF THE WATER AND SEWER LINES. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 4) SHT.0723-P-ADF-07 - THE VENT SHALL BE NOT LESS 1/2 |
| | THE SIZE OF THE DRAIN SERVED PER 2010 FBC-PLUMBING, |
| | SEC. 916.1. THE MINIMUM VENT SIZE SHALL BE 2". |
| | 5) SHUTOFF VALVES ARE REQUIRED ON THE |
| | FIXTURES.FBC-PLUMBING SEC.606.2. |
| | 6) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED TO THE |
| | TOP OF THE GRIPPING SURFACE PER 2010 FBC-ACCESSIBILITY |
| | SEC. 609.4. |
| | 7) SHT. A-ADF-06 - THE ENLARGED TOILET ROOM PLAN - SHOW |
| | THE CLEAR INSIDE LENGTH AND WIDTH DIMENSIONS FOR THE |
| | TOILET ROOM. |
| | 8) THE LAVATORY APPEARS TO BE ENCROACHING INTO THE |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET. THIS IS NOT |
| | ALLOWED PER FBC-ACCESSIBILITY SEC.604.3. |
| | 9) IF THE LEADING EDGE OF THE "HI" SIDE DRINKING |
| | FOUNTAIN IS MORE THAN 27 INCHES ABOVE THE FINISH FLOOR |
| | IN CAN ONLY PROJECT INTO THE CIRCULATION PATH 4 INCHES |
| | PER 2010 FBC-ACCESSIBILITY SEC.307.2. A SKIRT MAY BE |
| | REQUIRED TO BE PLACED ON THE UNIT TO MEET COMPLIANCE. |
| | 10) A SERVICE SINK IS REQUIRED FOR THIS OCCUPANCY PER |
| | TABLE 403.1. |
| | 11) TABLE 403.1 OF 2010 FBC- PLUMBING REQUIRES SEPARATE |
| | FACILITIES FOR MALES & FEMALES FOR THIS OCCUPANCY. YOU |
| | MAY REQUEST RELIEF FROM THIS REQUIREMENT TO THE |
| | PLUMBING OFFICIAL BY WRITTEN REQUEST. |
| | 12) THE OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN |
| | 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF |
| | COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO |
| | REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND |
| | PARAPET SCUPPERS PER 2010 FBC SEC.1503.4.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |