Plan Review Notes
Plan Review Notes For Permit 15060552
Permit Number 15060552
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-15 12:56:151ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060552 DIGESTER ELECTRICAL BUILDING
 7/15/15
  
 1) SUBMIT THE FOLLOWING ENERGY EFFICIENCY COMPLIANCE
 DOCUMENTS PREPARED BY THE ENGINEER OF RECORD: A)
 COOLING AND HEATING CALCULATIONS FOR AC-1, 2, & 3 IN
 ACCORDANCE WITH ACCA MANUAL N OR APPROVED ALTERNATE
 METHOD- SECTION 503.2.1 FBC-10 ENERGY CONSERVATION . B)
 ENERGY EFFICIENCY FORM 502-2010 OR 506-2010- REFERENCE
 SECTIONS 101.3, 103, AND CHAPTER 5 FBC-10 ENERGY
 CONSERVATION. THE DESIGN PROFESSIONAL SHALL CHOOSE
 EITHER THE PRESCRIPTIVE (502) OR PERFORMANCE BASED
 (506) COMPLIANCE PATH FOR THE BUILDING AND BUILDING
 SYSTEMS INCLUDING BUT NOT LIMITED TO THE COMPONENTS OF
 THE THERMAL ENVELOPE, THE HVAC, THE ELECTRICAL POWER,
 LIGHTING, AND CONTROLS.
 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE AC-
 1, 2, & 3.
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE PLAN
 IN COMPLIANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 PROVIDE A SCHEDULE ON THE PLAN INDICATING THE REQUIRED
 CFM'S OF O/A, AND THE TOTAL CFM'S TO BE PROVIDED.
 4) SHEET H-ADF-08: PROVIDE A SEQUENCE OF OPERATION FOR
 THE AC SYSTEMS, INCLUDING HOW THE O/A INTAKES WILL BE
 CONTROLLED- REFERENCE SECTION 503.2.5.3 FBC-10 ENERGY
 CONSERVATION. WILL MOTORIZED DAMPERS BE INSTALLED?
 PLEASE NOTE THAT THERMOSTATS ARE NOT SHOWN ON THE PLAN
 FOR AC-1, & 2.
 5) PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE PLAN
 LISTING MAKES AND MODELS AND SIZES OF ALL COMPONENTS
 INCLUDING DUCTS, DIFFUSERS, AND RETURN GRILLS.
 6) PROVIDE TYPICAL DUCT HANGING AND CONNECTION DETAILS
 IN ACCORDANCE WITH THE SMACNA 2005 STANDARD.
 7) PROVIDE TESTED AND APPROVED FIRE STOPPING SYSTEM
 DETAILS FOR ALL PIPES OR DUCTS PENETRATING FIRE-RATED
 WALLS.
 8) H-ADF-08: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY DUCTS OF AC- 1 & 2: PLEASE PROVIDE A SYMBOL ON
 THE PLAN TO SHOW THEIR LOCATIONS AND PROVIDE AN
 INSTALLATION DETAIL ON THE PLAN- SECTION 606.2.1 FBC-10
 MECHANICAL. PROVIDE INSTALLATION DETAILS FOR THE
 DEVICES, AND HOW THEY WILL BE SUPERVISED PER SECTION
 606.4.1.
 9) H-ADF-08: PROVIDE STRUCTURAL DETAILS FOR
 INSTALLATION OF THE CONDENSER PADS AND ENGINEERED WIND
 LOAD TIE-DOWN DETAILS FOR MOUNTING AC- 1 & 2 TO THE
 PADS- SECTION 301.12 FBC-10 MECHANICAL.
 10) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR
 INSTALLATION OF AC-3 ON THE ROOF INCLUDING A SECTION
 VIEW SHOWING THE STRUCTURAL COMPONENTS OF THE CURB,
 ANCHORING OF THE CURB TO THE ROOF STRUCTURE, MOUNTING
 OF THE AC UNIT TO THE CURB, AND THE CURB HEIGHT ABOVE
 THE FINISHED ROOF- SECTION 301.12.
 11) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF ALL
 EQUIPMENT AND REQUIRED CLEARANCE DISTANCE MEASUREMENTS.
 SHOW THE LOCATIONS OF THE ROOF LADDERS AND PROVIDE
 DETAILS FOR CONSTRUCTION OF THE LADDERS INDICATING
 COMPLIANCE WITH THE DESIGN CRITERIA LISTED IN SECTION
 306.5 FBC-10 MECHANICAL.
 12) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 13) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPES SERVICING EACH TANK,
 FACILITY, OR BUILDING.
 14) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES A)
 FLORIDA PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S FOR
 ALL PRODUCTS REGULATED BY FAC RULE 9N-3 REVIEWED AND
 APPROVED IN WRITING BY THE DESIGN PROFESSIONAL OF
 RECORD (HVAC ROOF CURBS, EXHAUST FANS AND CURBS,
 EXHAUST AND INTAKE LOUVERS, ETC.). B) MANUFACTURER'S
 PRODUCT DATA SHEETS FOR THE AC SYSTEMS, ROOF MOUNTED
 EXHAUST FANS, DS DETECTORS, O/A DAMPERS, ELECTRONIC
 CONTROLS, PIPINGS AND FITTINGS, AND PIPE INSULATION
 ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  