2015-10-30 17:05:163RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060551
 10/30/15
  
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS: THIS IS
 THE THIRD REQUEST FOR THE SEQUENCE OF OPERATION FOR THE
 AC SYSTEMS. SEE SHEET H-ADF-01, NOTE #4 AND PROVIDE
 DETAILS ON THE PLAN.
 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS: THE
 DIAGRAMS PROVIDED ON SHEET I-ADF-20 DO NOT COMPLETELY
 ANSWER THE COMMENT: PLEASE PROVIDE THE REQUESTED
 NARRATIVE, SHOW THE ACTUAL LOCATIONS OF THE DETECTORS,
 AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 2) COMMENT #10: 3RD REQUEST FOR DUCT SMOKE DETECTORS TO
 BE INSTALLED IN THE AC SUPPLY AIR SYSTEMS- REFER TO
 SECTION 606.2.1 FBC-10 MECHANICAL. SHEET H-ADF-06 SHOWS
 THE DEVICES ONLY IN THE EXHAUST PLENUMS.
 4) NOTE: AS PREVIOUSLY COMMENTED, SITE SPECIFIC WIND
 LOAD ENGINEERING FOR ATTACHMENT OF THE FANS, FAN CURBS,
 AND AC UNITS IS REQUIRED PER SECTION 301.13. THE
 DETAILS ON SHEET H-STD-3 ARE INCOMPLETE AND NOT IN
 COMPLIANCE.
  