| 2015-10-30 17:05:16 | 3RD REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15060551 |
| | 10/30/15 |
| | |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS: THIS IS |
| | THE THIRD REQUEST FOR THE SEQUENCE OF OPERATION FOR THE |
| | AC SYSTEMS. SEE SHEET H-ADF-01, NOTE #4 AND PROVIDE |
| | DETAILS ON THE PLAN. |
| | 2) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS: THE |
| | DIAGRAMS PROVIDED ON SHEET I-ADF-20 DO NOT COMPLETELY |
| | ANSWER THE COMMENT: PLEASE PROVIDE THE REQUESTED |
| | NARRATIVE, SHOW THE ACTUAL LOCATIONS OF THE DETECTORS, |
| | AND PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE |
| | DESIGN PROFESSIONAL OF RECORD. |
| | 2) COMMENT #10: 3RD REQUEST FOR DUCT SMOKE DETECTORS TO |
| | BE INSTALLED IN THE AC SUPPLY AIR SYSTEMS- REFER TO |
| | SECTION 606.2.1 FBC-10 MECHANICAL. SHEET H-ADF-06 SHOWS |
| | THE DEVICES ONLY IN THE EXHAUST PLENUMS. |
| | 4) NOTE: AS PREVIOUSLY COMMENTED, SITE SPECIFIC WIND |
| | LOAD ENGINEERING FOR ATTACHMENT OF THE FANS, FAN CURBS, |
| | AND AC UNITS IS REQUIRED PER SECTION 301.13. THE |
| | DETAILS ON SHEET H-STD-3 ARE INCOMPLETE AND NOT IN |
| | COMPLIANCE. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |