| 2015-10-20 08:45:22 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING & |
| | BOILER/ GAS HANDILING BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 09/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID. |
| | |
| | 1-5) COMPLIED. |
| | |
| | 6) 3RD. REQUEST. |
| | |
| | 6A) THE RESPONSE COMMENTS INDICATE THE ROOF PRESSURES |
| | ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN THIS |
| | PERMIT PACKAGE. SHEET 0283 THEN JUMPS TO 0286. RESPONSE |
| | INDICATE THIS IS FOR T1 & T2 SLUDGE PUMPING ROOF? THIS |
| | IS FOR THE M1-M4 SLUDGE PUMPING & BOILER/ GAS HANDILING |
| | BUILDING. |
| | 0386-A-ADF-08 BUILT -UP ROOF W/ 4 INCHES OF INSULATION/ |
| | EXHAUST FANS & ROOF CURBS FOR EXHAUST FANS AS WELL AS |
| | ROOF TOP RTU'S. |
| | NOTE OVER A 3'-0" PARAPET ZONE 3 PRESSURES ARE TO BE |
| | THE SAME AS ZONE 2 PRESSURES. COMPONENTS AND CLADDING |
| | 2010 FBC-B 1609.3/ TABLE 1609.2(2). |
| | |
| | 6B) THE RESPONSE TO WHERE THE DOOR PRESSURES ARE FOUND |
| | IS ON SHEET 0365-A-GEN.01. THE WALL PRESSURES ARE IN |
| | VULT, IT IS ASSUMED THAT THE PRESSURES GIVEN ARE FOR |
| | THE SQUARE FOOTAGE OF THE OPENING. THEY ARE LOW AND ARE |
| | FOR WALL ZONE NUMBER 4 THE INTERIOR ZONE, THE PRESSURES |
| | FOR 180 VULT. APPEAR TO BE FOR EXPOSURE B AT A MEAN |
| | ROOF HEIGHT OF 25 FT. TABLE 1609.7.2 HEIGHT AND |
| | EXPOSURE ADJUSTMENT COEFFICIENT. |
| | |
| | 6C) THE DOOR SCHEDULE FOUND ON SHEET 0365-A-GEN.02 DOES |
| | IDENTIFY THE DOORS BY NUMBERS, ON WHICH SHEET DO WE |
| | LOOK TO VERIFY THE LOCATION OF THE DOORS TO SEE IF THEY |
| | ARE IN ZONE 4 OR END ZONE 5. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED TO DETRMINE WALL ZONE 4 OR WALL |
| | ZONE 5. |
| | |
| | 6D) PLEASE PROVIDE WHERE THE WALL LOUVER PRESSURES CAN |
| | BE LOCATED TO VERIFY COMPLIANCE WITH PRESSURES. ) |
| | COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9-11) COMPLIED. |
| | |
| | 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO : |
| | EXPOSURE "C" @ 180 MPH, 25 FT ABOVE GRADE,@ 10 SQ. FT. |
| | : |
| | VULT FOR ROOF, ZONE 1 -78.70 , ZONE 2 -132.03 & ZONE 3 |
| | -132.03 (3 FT. PARAPET). |
| | VASD FOR ROOF, ZONE 1 -47.22. ZONE 2 -79.21 & ZONE 3 |
| | -79.21 (3 FT. PARAPET). |
| | |
| | 12B) COMPLIED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 0365-A-ADF-02 BOILER GAS HANDLING BUILDING |
| | 0382-A-ADF-04 FLOOR PLAN |
| | 0386-A-ADF-08 ROOF PLAN |
| | 0390-A-ADF-12 ELEVATIONS |
| | 0391-A-ADF-13 ELEVATIONS |
| | 0281-S-ADF-15 FOUNDATION |
| | 0284-S-ADF-18 ROOF |
| | 0287-S-ADF-21 SECTIONS |
| | 0365-A-GEN-02 DOOR SCHEDULE |