2015-10-20 08:45:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. OCT. 09/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1-5) COMPLIED.
  
 6) 3RD. REQUEST.
  
 6A) THE RESPONSE COMMENTS INDICATE THE ROOF PRESSURES
 ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN THIS
 PERMIT PACKAGE. SHEET 0283 THEN JUMPS TO 0286. RESPONSE
 INDICATE THIS IS FOR T1 & T2 SLUDGE PUMPING ROOF? THIS
 IS FOR THE M1-M4 SLUDGE PUMPING & BOILER/ GAS HANDILING
 BUILDING.
 0386-A-ADF-08 BUILT -UP ROOF W/ 4 INCHES OF INSULATION/
 EXHAUST FANS & ROOF CURBS FOR EXHAUST FANS AS WELL AS
 ROOF TOP RTU'S.
 NOTE OVER A 3'-0" PARAPET ZONE 3 PRESSURES ARE TO BE
 THE SAME AS ZONE 2 PRESSURES. COMPONENTS AND CLADDING
 2010 FBC-B 1609.3/ TABLE 1609.2(2).
  
 6B) THE RESPONSE TO WHERE THE DOOR PRESSURES ARE FOUND
 IS ON SHEET 0365-A-GEN.01. THE WALL PRESSURES ARE IN
 VULT, IT IS ASSUMED THAT THE PRESSURES GIVEN ARE FOR
 THE SQUARE FOOTAGE OF THE OPENING. THEY ARE LOW AND ARE
 FOR WALL ZONE NUMBER 4 THE INTERIOR ZONE, THE PRESSURES
 FOR 180 VULT. APPEAR TO BE FOR EXPOSURE B AT A MEAN
 ROOF HEIGHT OF 25 FT. TABLE 1609.7.2 HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENT.
  
 6C) THE DOOR SCHEDULE FOUND ON SHEET 0365-A-GEN.02 DOES
 IDENTIFY THE DOORS BY NUMBERS, ON WHICH SHEET DO WE
 LOOK TO VERIFY THE LOCATION OF THE DOORS TO SEE IF THEY
 ARE IN ZONE 4 OR END ZONE 5. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO DETRMINE WALL ZONE 4 OR WALL
 ZONE 5.
  
 6D) PLEASE PROVIDE WHERE THE WALL LOUVER PRESSURES CAN
 BE LOCATED TO VERIFY COMPLIANCE WITH PRESSURES. )
 COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-11) COMPLIED.
  
 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO :
 EXPOSURE "C" @ 180 MPH, 25 FT ABOVE GRADE,@ 10 SQ. FT.
 :
 VULT FOR ROOF, ZONE 1 -78.70 , ZONE 2 -132.03 & ZONE 3
 -132.03 (3 FT. PARAPET).
 VASD FOR ROOF, ZONE 1 -47.22. ZONE 2 -79.21 & ZONE 3
 -79.21 (3 FT. PARAPET).
  
 12B) COMPLIED.
  
 13) COMPLIED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 0365-A-ADF-02 BOILER GAS HANDLING BUILDING
 0382-A-ADF-04 FLOOR PLAN
 0386-A-ADF-08 ROOF PLAN
 0390-A-ADF-12 ELEVATIONS
 0391-A-ADF-13 ELEVATIONS
 0281-S-ADF-15 FOUNDATION
 0284-S-ADF-18 ROOF
 0287-S-ADF-21 SECTIONS
 0365-A-GEN-02 DOOR SCHEDULE