Plan Review Notes
Plan Review Notes For Permit 15060551
Permit Number 15060551
Review Stop P
Sequence Number 2
Notes
Date Text
2015-10-06 11:24:281) THE NARRATIVE RESPONSE TO REVIEW COMMENTS REFERS TO
 DRAWING 0456-I-ADF -20 FOR DETAILS FOR THE GAS DETECTOR
 INFO. THIS DRAWING IS NOT INCLUDED IN THIS PEMIT
 PACKAGE. PLEASE INCLUDE THIS DRAWING FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SHT. 0167-M-ADF-34 DOES NOT PROVIDE ANY OF THE
 REQUIRED INFORMATION PREVIOUSLY REQUESTED FOR THE GAS
 RISER DIAGRAM.NEITHER DOES SHT.0164-M-ADF-31.SINCE THIS
 INFORMATION HAS NOT BEEN SUBMITTED THE PLAN WILL BE
 MARKED THAT A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 GAS AND ALL REQUIRED INFO WILL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION SUBMITTAL ALONG WITH ALL NEW
 DRAWINGS OR SUBMIT ALL THE INFORMATION AS PREVIOUSLY
 REQUESTED.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE
 NARRATIVE RESPONSES TO THE GAS COMMENTS DO NOT PROVIDE
 SUFFICIENT INFO TO DO A COMPREHENSIVE REVIEW.
 3) SHT.0386-A-ADF-08 - DETAIL # 0763010 & NOTE #2 -
 NOTE # 2 STATES THE OVERFLOW SCUPPER WILL BE 3 INCHES
 ABOVE THE PRIMARY SCUPPER. INCLUDE IN THE NOTE THAT THE
 OVERFLOW SCUPPER SHALL BE NO LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF SURFACE.THIS
 IS THE LANGUAGE IN THE CODE.NOTE #2 STATES "3 INCHES
 ABOVE THE PRIMARY SCUPPER". THIS COULD BE
 MISINTERPRETED AS MEANING THE TOP OF THE SCUPPER.
 4) SHT. 0385-A-ADF-7- THE ROOF DRAINAGE CALCULATIONS
 SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES PER HOUR
 AS THERE IS NO 4.5 INCH RAINFALL RATE IN ANY OF THE
 SIZING TABLES.THE ALLOWABLE SQUARE FOOT AREA TO BE
 DRAINED BY EACH DRAIN/SCUPPER WILL HAVE TO BE ADJUSTED.
 5) THE NARRATIVE RESPONSE FOR PREVIOUS COMMENT # 9 DOES
 NOT COMPLY WITH SEC.905.2. THE VENT CONNECTION SHALL BE
 SO GRADED AND CONNECTED AS TO DRAIN BACK TO THE
 DRAINAGE PIPE BY GRAVITY. AS DRAWN, IT IS INSTALLED TO
 DRAIN BACK TO THE FIXTURE TO WHICH IT IS CONNECTED.IT
 DOES NOT COMPLY WITH 2010 FBC-PLUMBING SEC.706.3 &
 905.2.THE FITTING SHALL BE INSTALLED IN THE DIRECTION
 OF FLOW.AS DRAWN IT IS NOT.
 6) SHT.0696-H-ADF-01 REFERS TO TWO DIFFERENT STANDARDS
 FOR CALCULATING COMBUSTION AIR REQUIREMENTS. THE CODE
 IN EFFECT IS THE 2010 FBC-FUEL GAS. THE APPROPRIATE
 SECTION FOR USING TWO OPENINGS COMMUNICATING DIRECTLY
 WITH THE OUTDOORS IF 304.6.1. THE FORMULA IS A MINIMUM
 FREE AREA OF 1 SQUARE INCH PER 4000/ BTU OF TOTAL INPUT
 RATING OF ALL APPLIANCES IN THE ENCLOSURE. PLEASE
 EXPLAIN WHERE THE .47 FREE AREA COMES FROM IN YOUR
 EQUATION. SEC.304.10 OF 2010 FBC-FUEL GAS SPECIFIES
 METAL LOUVERS AND GRILLS WILL HAVE 75% FREE AREA. THE
 DESIGN MEETS THE REQUIRED COMBUSTION AIR BUT NOTES # 3
 & #4 ON SHT 0696-H-ADF-01 NEED TO BE REVISED.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  