| Date |
Text |
| 2015-10-06 11:24:28 | 1) THE NARRATIVE RESPONSE TO REVIEW COMMENTS REFERS TO |
| | DRAWING 0456-I-ADF -20 FOR DETAILS FOR THE GAS DETECTOR |
| | INFO. THIS DRAWING IS NOT INCLUDED IN THIS PEMIT |
| | PACKAGE. PLEASE INCLUDE THIS DRAWING FOR REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHT. 0167-M-ADF-34 DOES NOT PROVIDE ANY OF THE |
| | REQUIRED INFORMATION PREVIOUSLY REQUESTED FOR THE GAS |
| | RISER DIAGRAM.NEITHER DOES SHT.0164-M-ADF-31.SINCE THIS |
| | INFORMATION HAS NOT BEEN SUBMITTED THE PLAN WILL BE |
| | MARKED THAT A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | GAS AND ALL REQUIRED INFO WILL BE SUBMITTED AT TIME OF |
| | PERMIT APPLICATION SUBMITTAL ALONG WITH ALL NEW |
| | DRAWINGS OR SUBMIT ALL THE INFORMATION AS PREVIOUSLY |
| | REQUESTED.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE |
| | NARRATIVE RESPONSES TO THE GAS COMMENTS DO NOT PROVIDE |
| | SUFFICIENT INFO TO DO A COMPREHENSIVE REVIEW. |
| | 3) SHT.0386-A-ADF-08 - DETAIL # 0763010 & NOTE #2 - |
| | NOTE # 2 STATES THE OVERFLOW SCUPPER WILL BE 3 INCHES |
| | ABOVE THE PRIMARY SCUPPER. INCLUDE IN THE NOTE THAT THE |
| | OVERFLOW SCUPPER SHALL BE NO LESS THAN 2 INCHES NOR |
| | MORE THAN 4 INCHES ABOVE THE FINISHED ROOF SURFACE.THIS |
| | IS THE LANGUAGE IN THE CODE.NOTE #2 STATES "3 INCHES |
| | ABOVE THE PRIMARY SCUPPER". THIS COULD BE |
| | MISINTERPRETED AS MEANING THE TOP OF THE SCUPPER. |
| | 4) SHT. 0385-A-ADF-7- THE ROOF DRAINAGE CALCULATIONS |
| | SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES PER HOUR |
| | AS THERE IS NO 4.5 INCH RAINFALL RATE IN ANY OF THE |
| | SIZING TABLES.THE ALLOWABLE SQUARE FOOT AREA TO BE |
| | DRAINED BY EACH DRAIN/SCUPPER WILL HAVE TO BE ADJUSTED. |
| | 5) THE NARRATIVE RESPONSE FOR PREVIOUS COMMENT # 9 DOES |
| | NOT COMPLY WITH SEC.905.2. THE VENT CONNECTION SHALL BE |
| | SO GRADED AND CONNECTED AS TO DRAIN BACK TO THE |
| | DRAINAGE PIPE BY GRAVITY. AS DRAWN, IT IS INSTALLED TO |
| | DRAIN BACK TO THE FIXTURE TO WHICH IT IS CONNECTED.IT |
| | DOES NOT COMPLY WITH 2010 FBC-PLUMBING SEC.706.3 & |
| | 905.2.THE FITTING SHALL BE INSTALLED IN THE DIRECTION |
| | OF FLOW.AS DRAWN IT IS NOT. |
| | 6) SHT.0696-H-ADF-01 REFERS TO TWO DIFFERENT STANDARDS |
| | FOR CALCULATING COMBUSTION AIR REQUIREMENTS. THE CODE |
| | IN EFFECT IS THE 2010 FBC-FUEL GAS. THE APPROPRIATE |
| | SECTION FOR USING TWO OPENINGS COMMUNICATING DIRECTLY |
| | WITH THE OUTDOORS IF 304.6.1. THE FORMULA IS A MINIMUM |
| | FREE AREA OF 1 SQUARE INCH PER 4000/ BTU OF TOTAL INPUT |
| | RATING OF ALL APPLIANCES IN THE ENCLOSURE. PLEASE |
| | EXPLAIN WHERE THE .47 FREE AREA COMES FROM IN YOUR |
| | EQUATION. SEC.304.10 OF 2010 FBC-FUEL GAS SPECIFIES |
| | METAL LOUVERS AND GRILLS WILL HAVE 75% FREE AREA. THE |
| | DESIGN MEETS THE REQUIRED COMBUSTION AIR BUT NOTES # 3 |
| | & #4 ON SHT 0696-H-ADF-01 NEED TO BE REVISED. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |