Plan Review Notes
Plan Review Notes For Permit 15060551
Permit Number 15060551
Review Stop M
Sequence Number 2
Notes
Date Text
2015-10-14 08:12:142ND REVIEW: FBC 2010 MECHANICAL
 PERMIT 15060551
 10/14/15
  
 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW, THE
 SUBMITTED NARRATIVE STATES THAT THE PROPOSED BUILDING
 IS EXEMPT FROM THE FLORIDA ENERGY CODE UNDER FAC RULE
 61G20-1.001. I WAS UNABLE TO FIND ANY LANGUAGE IN THE
 RULE SUPPORTING THAT CLAIM. PLEASE SEE SECTION
 C101.4.8.4 FBC-14 ENERGY CONSERVATION AND INDICATE
 WHICH OF THE 5 EXEMPTIONS LISTED PERTAINS TO THE
 PROPOSED BUILDING.
 2) IN RESPONSE TO COMMENT #2 THE NARRATIVE STATES THAT
 AIR HANDLER SCHEDULES ARE ON SHEET H0SCD-03, AND
 EXHAUST FAN SCHEDULES ON H-SCH-01. I WAS UNABLE TO FIND
 THESE SHEETS IN THE UPLOADED PLAN INDEX. PLEASE REVIEW
 AND PROVIDE THE PLAN SHEETS.
 3) IN RESPONSE TO COMMENT #3 THE NARRATIVE STATES THAT
 THE VENTILATION SYSTEM SEQUENCE OF OPERATION IS IN THE
 SPEC BOOK. PLEASE PROVIDE THE REQUESTED SEQUENCE ON THE
 PLANS FOR REVIEW AND INSPECTION PURPOSES.
 4) IN RESPONSE TO COMMENT #4 THE NARRATIVE STATES
 DETAILS TO BE FOUND ON SHEET 0456-I-ADF-20: THIS PLAN
 SHEET NOT UPLOADED.
 5) COMMENT #5: PER NARRATIVE RESPONSE, THE REQUESTED
 BOILER VENTING DETAILS ARE DEFERRED PENDING SUBMITTAL
 OF SHOP DRAWINGS.
 6) COMMENT #7: THE NARRATIVE STATES THE AIR
 DISTRIBUTION SCHEDULE IS ON SHEET H-SCHD-02: THIS PLAN
 SHEET NOT UPLOADED.
 7) COMMENT #10: AS PREVIOUSLY REQUESTED PROVIDE A
 SYMBOL FOR THE DS DETECTOR IN THE SUPPLY DUCTS SHOWN ON
 SHEET H-ADF-02.
 8) COMMENT #12: PER NARRATIVE RESPONSE, THE REQUESTED
 WIND LOAD TIE DOWN DETAILS ARE DEFERRED PENDING
 SUBMITTAL OF MANUFACTURER'S SHOP DRAWINGS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  