| 2015-10-09 07:00:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING & |
| | BOILER/ GAS HANDILING BUILDING |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. OCT. 09/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID. |
| | |
| | 1) RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER |
| | ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE |
| | COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON |
| | THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE |
| | COMMENT RESPONSE. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 1ST REVIEW COMMNETS. PLEASE EITHER REMOVE THE INDEX |
| | SHEETS 0002-6-GEN.02 THROUGH 0005-6-GEN.05 OR VOID THEM |
| | OUT THEY ARE OF NO USE TO THIS PROJECT THE WAY IT WAS |
| | SUBMITTED. THE PLANS DO NOT FOLLOW THE INDEX BEING |
| | BROUGHT IN BY BUILDING TYPES. 107.2.1.4 QUALITY OF |
| | BUILDING PLANS. |
| | |
| | 2-5) COMPLIED. |
| | |
| | |
| | |
| | |
| | 6) 2ND REQUEST. THE RESPONSE COMMENTS INDICATE THE ROOF |
| | PRESSURES ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN |
| | THIS PERMIT PACKAGE. THE RESPONSE TO WHERE THE WINDOW |
| | AND POOR PRESSURES ARE FOUND IS ON SHEET 0364-A-GEN.01 |
| | THE REMAINDER OF THE RESPONSE IS CUT OFF. THIS SHEET |
| | DOES SHOW WALL PRESSUREES FOR THESE WINDOW TYPES, BUT |
| | THEY CAN ONLY BE ASSUMPTIONS. THE PROBLEM WE HAVE AS |
| | PLAN REVIEWERS AND INSPECTORS IS THE LIMITED AMOUNT OF |
| | TIME TO FIND DOCUMENTATION. WHEN THE WIND DESIGN |
| | CRITERIA IS NOT GIVEN ON THE SAME PAGE WE ARE ONLY |
| | MAKING A ASSUMPTION, IS THE DESIGN TO 170 OR 180 MPH, |
| | EXPOSUSRE B OR C , THE MEAN ROOF HEIGHT OF THE BUILDING |
| | ARE THE PRESSURES REPRESENTED VULT OR VASD. |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 1ST REVIEW COMMENT.PLEASE PROVIDE WHERE THE PRESSURES |
| | FOR COMPONENTS & CLADDING CAN BE FOUND. SHEET |
| | 0283-S-ADF-17 T1 & T2 SLUDGE PUMPING ROOF PLAN DOES NOT |
| | PROVIDE THE PRESSURES FOR ROOF ZONES 1,2,3 NOR THE WALL |
| | ZONES 4 & 5. |
| | |
| | |
| | 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9-11) COMPLIED. |
| | |
| | 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO : |
| | EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE, VASD FOR |
| | ROOF, ZONE 1 -40.40, ZONE 2 -67.76 & ZONE 3 -101.9. |
| | |
| | 1ST REVIEW. SHEET 0284-S-ADF-18 PRESSURES FOR |
| | COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 20 FT |
| | ABOVE GRADE, VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE |
| | PRESSURES AT 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 2010 FBC-B |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | 12B). RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER |
| | ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE |
| | COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON |
| | THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE |
| | COMMENT RESPONSE. |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 1ST REQUEST. SHEET 0284-S-ADF-01 THRU -S-ADF- 40 NO |
| | PRESSURES FOR THE DOOR OPENINGS ARE NOT PROVIDED FOR |
| | THIS BUILDING. 2010 FBC-B 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |