Plan Review Notes
Plan Review Notes For Permit 15060551
Permit Number 15060551
Review Stop B
Sequence Number 2
Notes
Date Text
2015-10-09 07:00:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: TBD/ TO BE DETERMINED
 CONTACT: KURT PFEFFER, P. E.
 TEL: (561)997-8070
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. OCT. 09/ 2015
 ACTION: DENIED
  
 NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART
 OF ANY PLAN REVIEW IF SUBMITED THEY GET STAMPED VOID.
  
 1) RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER
 ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE
 COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON
 THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE
 COMMENT RESPONSE.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 1ST REVIEW COMMNETS. PLEASE EITHER REMOVE THE INDEX
 SHEETS 0002-6-GEN.02 THROUGH 0005-6-GEN.05 OR VOID THEM
 OUT THEY ARE OF NO USE TO THIS PROJECT THE WAY IT WAS
 SUBMITTED. THE PLANS DO NOT FOLLOW THE INDEX BEING
 BROUGHT IN BY BUILDING TYPES. 107.2.1.4 QUALITY OF
 BUILDING PLANS.
  
 2-5) COMPLIED.
  
  
  
  
 6) 2ND REQUEST. THE RESPONSE COMMENTS INDICATE THE ROOF
 PRESSURES ARE FOUND ON 0284-ADF18, THAT SHEET IS NOT IN
 THIS PERMIT PACKAGE. THE RESPONSE TO WHERE THE WINDOW
 AND POOR PRESSURES ARE FOUND IS ON SHEET 0364-A-GEN.01
 THE REMAINDER OF THE RESPONSE IS CUT OFF. THIS SHEET
 DOES SHOW WALL PRESSUREES FOR THESE WINDOW TYPES, BUT
 THEY CAN ONLY BE ASSUMPTIONS. THE PROBLEM WE HAVE AS
 PLAN REVIEWERS AND INSPECTORS IS THE LIMITED AMOUNT OF
 TIME TO FIND DOCUMENTATION. WHEN THE WIND DESIGN
 CRITERIA IS NOT GIVEN ON THE SAME PAGE WE ARE ONLY
 MAKING A ASSUMPTION, IS THE DESIGN TO 170 OR 180 MPH,
 EXPOSUSRE B OR C , THE MEAN ROOF HEIGHT OF THE BUILDING
 ARE THE PRESSURES REPRESENTED VULT OR VASD.
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1ST REVIEW COMMENT.PLEASE PROVIDE WHERE THE PRESSURES
 FOR COMPONENTS & CLADDING CAN BE FOUND. SHEET
 0283-S-ADF-17 T1 & T2 SLUDGE PUMPING ROOF PLAN DOES NOT
 PROVIDE THE PRESSURES FOR ROOF ZONES 1,2,3 NOR THE WALL
 ZONES 4 & 5.
  
  
 7) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 8) BUILDING PROVISO107.3.4.2 DEFERRED SUBMITTAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-11) COMPLIED.
  
 12A) 2ND REQUEST. EXTREMELY LOW. SHOULD BE CLOSE TO :
 EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE, VASD FOR
 ROOF, ZONE 1 -40.40, ZONE 2 -67.76 & ZONE 3 -101.9.
  
 1ST REVIEW. SHEET 0284-S-ADF-18 PRESSURES FOR
 COMPONENTS AND CLADDING EXPOSURE "C" @ 180 MPH, 20 FT
 ABOVE GRADE, VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE
 PRESSURES AT 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 2010 FBC-B
 1609.6.4.41 COMPONENTS & CLADDING
  
 12B). RESPONSE COMMENTS ARE CUT OFF AND FOUND FURTHER
 ALONG IN THE RESPONSE COMMENTS. PLEASE FORMAT RESPONSE
 COMMENTS INTO LANDSCAPE VIEW SO THE RESPONSES ARE ON
 THE SAME SHEET. YOU HAVE TO GUESS WHERE YOU ARE IN THE
 COMMENT RESPONSE.
 107.2.1.4 QUALITY OF BUILDING PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 1ST REQUEST. SHEET 0284-S-ADF-01 THRU -S-ADF- 40 NO
 PRESSURES FOR THE DOOR OPENINGS ARE NOT PROVIDED FOR
 THIS BUILDING. 2010 FBC-B 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING.
  
 13) COMPLIED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  