Plan Review Notes
Plan Review Notes For Permit 15060549
Permit Number 15060549
Review Stop P
Sequence Number 3
Notes
Date Text
2015-10-22 11:15:391) THE NARRATIVE RESPONSE TO THE PLAN REVIEW COMMENTS
 CANNOT BE READ. MOST OF THE COMMENTS AND NARRATIVE ARE
 CUT OFF AND CANNOT BE SEEN. WPB AMEND. TO FBC SEC.
 107.2.1. THE RESPONSE NARRATIVE THAT WAS SUBMITTED IS
 DATED JUNE 17, 2015.
 2) IT DOES NOT APPEAR AS THOUGH ANY OF THE PLUMBING
 COMMENTS FROM THE 7/21/15 REVIEW HAVE BEEN ADDRESSED.
 COMPLY WITH ALL PREVIOUS PLUMBING PLAN REVIEW
 COMMENTS.SEE PREVIOUS COMMENTS BELOW.
  
 7/21/15 COMMENTS:
  
 1) SHT. 0385-A-ADF-7- THE ROOF DRAINAGE CALCULATIONS
 SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES PER HOUR
 AS THERE IS NO 4.5 INCH RAINFALL RATE IN ANY OF THE
 SIZING TABLES.THE ALLOWABLE SQUARE FOOT AREA TO BE
 DRAINED BY EACH DRAIN/SCUPPER WILL HAVE TO BE ADJUSTED.
 2) INDICATE THE HEAD IN INCHES THAT WAS USED IN THE
 SIZING OF THE SCUPPERS.SEE TABLE 1106.7 OF 2010 FPC.
 3) OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN 2
 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS PER THE 2010 FL. BUILDING CODE
 SEC.1503.4.2.1. NOTE # 2 STATES THE OVERFLOW SCUPPER
 WILL BE 3 INCHES ABOVE THE PRIMARY SCUPPER. INCLUDE IN
 THE NOTE THAT THE OVERFLOW SCUPPER SHALL BE NO LESS
 THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED
 ROOF SURFACE.THIS IS THE LANGUAGE IN THE CODE.NOTE #2
 STATES "3 INCHES ABOVE THE PRIMARY SCUPPER". THIS COULD
 BE MISINTERPRETED AS MEANING THE TOP OF THE SCUPPER.
 4) SHT.0385-A-ADF-07 - INDICATE ON THE PLANS THAT 1/2
 OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS RAINWATER
 TO THE ROOF HAS BEEN ADDED TO THE PROJECTED ROOF AREA
 PERR THE FPC SEC.1106.4.
 5) SEE TABLE 1106.7 OF FL.PLUMBING CODE FOR SCUPPER
 SIZING, NOT TABLE 1106.3 AS NOTED ON THE PLAN.
  
 NOTE: THIS IS THE THIRD TIME I HAVE REQUESTED THIS
 INFORMATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 1) SHT.0386-A-ADF-08 - DETAIL # 0763010 & NOTE #2 -
 NOTE # 2 STATES THE OVERFLOW SCUPPER WILL BE 3 INCHES
 ABOVE THE PRIMARY SCUPPER. INCLUDE IN THE NOTE THAT THE
 OVERFLOW SCUPPER SHALL BE NO LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF SURFACE.THIS
 IS THE LANGUAGE IN THE CODE.NOTE #2 STATES "3 INCHES
 ABOVE THE PRIMARY SCUPPER". THIS COULD BE
 MISINTERPRETED AS MEANING THE TOP OF THE SCUPPER.
 2) SHT. 0385-A-ADF-7- THE ROOF DRAINAGE CALCULATIONS
 SHALL BE BASED ON A RAINFALL RATE OF 5 INCHES PER HOUR
 AS THERE IS NO 4.5 INCH RAINFALL RATE IN ANY OF THE
 SIZING TABLES.THE ALLOWABLE SQUARE FOOT AREA TO BE
 DRAINED BY EACH DRAIN/SCUPPER WILL HAVE TO BE ADJUSTED.