Plan Review Notes
Plan Review Notes For Permit 15060549
Permit Number 15060549
Review Stop P
Sequence Number 2
Notes
Date Text
2015-10-05 12:42:511) THE NARRATIVE RESPONSE TO THE PLAN REVIEW COMMENTS
 CANNOT BE READ. MOST OF THE COMMENTS AND NARRATIVE ARE
 CUT OFF AND CANNOT BE SEEN. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) IT DOES NOT APPEAR AS THOUGH ANY OF THE PLUMBING
 COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN ADDRESSED.
 COMPLY WITH ALL PREVIOUS PLUMBING PLAN REVIEW
 COMMENTS.SEE PREVIOUS COMMENTS BELOW.
  
 7/21/15 COMMENTS:
  
 1) SHT. 0385-A-ADF-07 - THE RAINFALL RATE THAT IS TO BE
 USED IN THE SIZING OF THE STORMWATER SYSTEM IS 5
 INCHES, NOT 4.5. SEE TABLE 1106.7 OF FL.PLUMBING CODE
 FOR SCUPPER SIZING, NOT TABLE 1106.3.
 2) INDICATE THE HEAD IN INCHES THAT WAS USED IN THE
 SIZING OF THE SCUPPERS.SEE TABLE 1106.7 OF 2010 FPC.
 3) OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN 2
 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS PER THE 2010 FL. BUILDING CODE
 SEC.1503.4.2.1.
 4) SHT.0385-A-ADF-07 - INDICATE ON THE PLANS THAT 1/2
 OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS RAINWATER
 TO THE ROOF SHALL BE ADDED TO THE PROJECTED ROOF AREA
 PERR THE FPC SEC.1106.4.
 5) SEE TABLE 1106.7 OF FL.PLUMBING CODE FOR SCUPPER
 SIZING, NOT TABLE 1106.3 AS NOTED ON THE PLAN.
  
  
  
  
  
  
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  