Plan Review Notes
Plan Review Notes For Permit 15060549
Permit Number 15060549
Review Stop M
Sequence Number 2
Notes
Date Text
2015-10-14 07:47:452ND REVIEW: FBC 2010 MECHANICAL
 PERMIT 15060549
 10/14/15
  
 1) IN RESPONSE TO COMMENT #1 FROM THE 1ST REVIEW, THE
 SUBMITTED NARRATIVE STATES THAT THE PROPOSED BUILDING
 IS EXEMPT FROM THE FLORIDA ENERGY CODE UNDER FAC RULE
 61G20-1.001. I WAS UNABLE TO FIND ANY LANGUAGE IN THE
 RULE SUPPORTING THAT CLAIM. PLEASE SEE SECTION
 C101.4.8.4 FBC-14 ENERGY CONSERVATION AND INDICATE
 WHICH OF THE 5 EXEMPTIONS LISTED PERTAINS TO THE
 PROPOSED BUILDING.
 2) IN RESPONSE TO COMMENT #3 THE NARRATIVE STATES THAT
 AIR HANDLER SCHEDULES ARE ON SHEET H0SCD-03, AND
 EXHAUST FAN SCHEDULES ON H-SCH-01. I WAS UNABLE TO FIND
 THESE SHEETS IN THE UPLOADED PLAN INDEX. PLEASE REVIEW
 AND PROVIDE THE PLAN SHEETS.
 3) IN RESPONSE TO COMMENT #4 THE NARRATIVE STATES THAT
 THE VENTILATION SYSTEM SEQUENCE OF OPERATION IS IN THE
 SPEC BOOK. PLEASE PROVIDE THE REQUESTED SEQUENCE ON THE
 PLANS FOR REVIEW AND INSPECTION PURPOSES.
 4) COMMENT #5: SHEET H-SCHD-02 IS NOT IN THE PLAN
 INDEX. PLEASE REVIEW AND PROVIDE THE PLAN SHEET.
 5) COMMENT #8: AS PREVIOUSLY REQUESTED PROVIDE A SYMBOL
 FOR THE DS DETECTOR IN THE SUPPLY DUCT SHOWN ON SHEET
 H-ADF-06.
 6) COMMENTS #2 & #9: AS REQUESTED IN THE RESPONSE
 NARRATIVE, THE REQUIRED PRODUCT APPROVALS AND
 ENGINEERED TIE-DOWN DETAILS FOR ROOFTOP HVAC EQUIPMENT
 AND APPLIANCES WILL BE DEFERRED UNTIL A LATER DATE
 PRIOR TO 1ST INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  