Plan Review Notes
Plan Review Notes For Permit 15060549
Permit Number 15060549
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-21 08:47:091) SHT. 0385-A-ADF-07 - THE RAINFALL RATE THAT IS TO BE
 USED IN THE SIZING OF THE STORMWATER SYSTEM IS 5
 INCHES, NOT 4.5. SEE TABLE 1106.7 OF FL.PLUMBING CODE
 FOR SCUPPER SIZING, NOT TABLE 1106.3.
 2) INDICATE THE HEAD IN INCHES THAT WAS USED IN THE
 SIZING OF THE SCUPPERS.SEE TABLE 1106.7 OF 2010 FPC.
 3) OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN 2
 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 COVERING AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO
 REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS PER THE 2010 FL. BUILDING CODE
 SEC.1503.4.2.1.
 4) SHT.0385-A-ADF-07 - INDICATE ON THE PLANS THAT 1/2
 OF THE AREA OF ANY VERTICAL WAL LTHAT DIVERTS RAINWATER
 TO THE ROOF SHALL BE ADDED TO THE PROJECTED ROOF AREA
 PERR THE FPC SEC.1106.4.
 5) TABLE 1106.7 SHALL BE USED IN THE DESIGN OF THE ROOF
 SCUPPERS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  