| 2015-07-06 13:59:21 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060549 (T1/T2) SLUDGE PUMPING BUILDING- |
| | 7/6/2015 |
| | |
| | 1) SUBMIT THE FOLLOWING ENERGY EFFICIENCY COMPLIANCE |
| | DOCUMENTS PREPARED BY THE ENGINEER OF RECORD: A) |
| | COOLING AND HEATING CALCULATIONS FOR AHU 5 & 6 IN |
| | ACCORDANCE WITH ACCA MANUAL N OR APPROVED ALTERNATE |
| | METHOD- SECTION 503.2.1 FBC-10 ENERGY CONSERVATION . B) |
| | ENERGY EFFICIENCY FORM 502-2010 OR 506-2010- REFERENCE |
| | SECTION 101.3, 103, AND CHAPTER 5 FBC-10 ENERGY |
| | CONSERVATION. THE DESIGN PROFESSIONAL SHALL CHOOSE |
| | EITHER THE PRESCRIPTIVE (502) OR PERFORMANCE BASED |
| | (506) COMPLIANCE PATH FOR THE BUILDING AND BUILDING |
| | SYSTEMS INCLUDING BUT NOT LIMITIED TO THE COMPONENTS OF |
| | THE THERMAL ENVELOPE, THE HVAC EQUIPMENT, THE HYDRONIC |
| | PIPING, AND THE ELECTRICAL POWER, LIGHTING, AND |
| | CONTROLS. |
| | 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES A) FLORIDA |
| | PRODUCT APPROVALS AND/OR MIAMI DADE NOA'S FOR ALL |
| | PRODUCTS REGULATED BY FAC RULE 9N-3 REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGN PROFESSIONAL OF |
| | RECORD (HVAC ROOF CURBS, EXHAUST FANS AND CURBS, |
| | EXHAUST AND INTAKE LOUVERS, ETC.). B) MANUFACTURER'S |
| | PRODUCT DATA SHEETS FOR THE AHU- 5 & 6, EXHAUST FANS, |
| | FIRE DAMPERS, DUCT SMOKE DETECTORS, O/A MOTORIZED |
| | DAMPERS, ELECTRONIC CONTROLS, PIPE INSULATION ETC. |
| | 3) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR AHU- 5 & |
| | 6, AND EF- 5 & 6. |
| | 4) PROVIDE A SEQUENCE OF OPERATION FOR THE VENTILATION |
| | SYSTEM TO CLARIFY HOW IT WILL FUNCTION- |
| | THERMOSTATICALLY, CONTINUOUSLY? |
| | 5) PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE PLAN |
| | LISTING MAKES AND MODELS AND SIZES OF ALL COMPONENTS |
| | INCLUDING DUCTS, DIFFUSERS, AND RETURN GRILLS. |
| | 6) PROVIDE TYPICAL DUCT HANGING AND CONNECTION DETAILS |
| | IN ACCORDANCE WITH THE SMACNA 2005 STANDARD. |
| | 7) PROVIDE TESTED AND APPROVED FIRE STOPPING SYSTEM |
| | DETAILS FOR ALL PIPES OR DUCTS PENETRATING FIRE-RATED |
| | WALLS. |
| | 8) H-ADF-06: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY DUCTS OF BOTH AHU- 5 & 6: PLEASE PROVIDE A |
| | SYMBOL ON THE PLAN TO SHOW THEIR LOCATIONS, PROVIDE AN |
| | INSTALLATION DETAILS, AND INDICATE HOW THE DEVICES WILL |
| | BE SUPERVISED PER SECTION 606.4.1. |
| | 9) H-ADF-07: ENGINEERED WIND LOAD TIE-DOWN DETAILS FOR |
| | MOUNTING THE AHU'S AND CURBS, AND THE EXHAUST FANS AND |
| | CURBS ON THE ROOF ARE REQUIRED PER SECTION 301.12. |
| | PLEASE PROVIDE DETAILS, OR PLACE A NOTE INDICATING ON |
| | WHICH STRUCTURAL OR ARCHITECTURAL SHEET THE DETAILS ARE |
| | LOCATED. PROVIDE ELEVATION AND PLAN VIEW DRAWINGS |
| | INDICATING THE STRUCTURAL COMPONENTS OF THE CURBS, AND |
| | SHOW THE CURB HEIGHTS ABOVE THE FINISHED ROOF. |
| | 10) PROVIDE SECTION VIEWS OF THE ROOF LADDERS TO |
| | INDICATE COMPLIANCE WITH THE DESIGN CRITERIA LISTED IN |
| | SECTION 306.5. |
| | 11) BASED ON THE SOILS REPORT- PIPE BEDDING AND |
| | DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH |
| | CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND |
| | HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH |
| | DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS |
| | AND THICKNESSES, COMPACTION AND BACKFILLING |
| | SPECIFICATIONS. |
| | 12) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL |
| | UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS |
| | DEPICTING THE UNDERGROUND PIPES SERVICING EACH TANK, |
| | FACILITY, OR BUILDING. |
| | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS |
| | AND FITTINGS, AND PIPE INSULATION REVIEWED AND APPROVED |
| | BY THE DESIGN PROFESSIONAL OF RECORD. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |