Plan Review Notes
Plan Review Notes For Permit 15060544
Permit Number 15060544
Review Stop E
Sequence Number 1
Notes
Date Text
2015-06-20 13:21:54APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL
 (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS
 SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 (1) BATHROOMS
  
 2) NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS.
 IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED
 BY OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
  
 3)NEC 210.52 (D) BATHROOMS.
 IN DWELLING UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE
 EDGE OF EACH BASIN.
  
 4) FBC-RESIDENTIAL 314 AND 315.SMOKE DETECTORS.
 PROVIDE AND INSTALL SMOKE DETECTORS AS REQUIRED FOR NEW
 CONSTRUCTION. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 5) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]