2015-07-06 10:40:061ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060543 DIGESTER M1- 7/6/15
  
 1) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 2) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 3) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS, AND PIPE INSULATION REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  