2015-07-18 05:49:111) REMOVE SHEETS M-ADF-05,06, & 07 THAT SHOW THE TWAS
 TANKS AND SUBMIT SHEETS M-ADF-8,9,10,12, & 13 THAT SHOW
 THE T1 TANKS.
 2) SHT. M-STD-09 - DETAIL # 1542102 SHOWS A WYE FOR THE
 VENT INSTALLED IN THE OPPOSITE DIRECTION OF FLOW.THE
 WYE FITTING SHALL BE FLIPPED TO SHOW THE CORRECT
 INSTALLATION. FPC 706.3.
  