| Plan Review Notes For Permit 15060538 |
| Permit Number |
15060538 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-07-18 05:49:11 | 1) REMOVE SHEETS M-ADF-05,06, & 07 THAT SHOW THE TWAS | | | TANKS AND SUBMIT SHEETS M-ADF-8,9,10,12, & 13 THAT SHOW | | | THE T1 TANKS. | | | 2) SHT. M-STD-09 - DETAIL # 1542102 SHOWS A WYE FOR THE | | | VENT INSTALLED IN THE OPPOSITE DIRECTION OF FLOW.THE | | | WYE FITTING SHALL BE FLIPPED TO SHOW THE CORRECT | | | INSTALLATION. FPC 706.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|