Plan Review Notes
Plan Review Notes For Permit 15060538
Permit Number 15060538
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-02 07:50:371ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060538 DIGESTER T1- 7/2/15
  
 1) REMOVE PLAN SHEETS M-ADF-05, 06, & 07 THAT SHOW THE
 TWAS TANKS AND REPLACE WITH SHEETS M-ADF- 8, 9, 10, 12,
 & 13 THAT SHOW THE T1 TANKS.
 2) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 3) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 4) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFIC TO EACH
 BUILDING, TANK, OR FACILITY ETC.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD.
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved