| Plan Review Notes For Permit 15060538 |
| Permit Number |
15060538 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-26 15:00:04 | | | | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR SITE LIGHTING. | | | | | | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN | | | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF | | | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT | | | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED | | | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR | | | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A | | | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN | | | ASTRONOMICAL TIME SWITCH. | | | | | | 2) 2010 FBC-BUILDING SECTION 1609 | | | PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES | | | INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|