| Notes |
| Date |
Text |
| 2016-01-08 08:34:16 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15060530 | | | 01/08/16 | | | | | | 1) AS PREVIOUSLY REQUESTED IN COMMENT #5 FROM THE 1ST | | | REVIEW, PROVIDE THE SEQUENCE OF OPERATION FOR THE DUCT | | | SMOKE DETECTORS INSTALLED IN AC-1 & 2 IN THE | | | ELECTRICAL. THE NOTES ON SHEET 0797-H-SEQ-01 DO NOT | | | SPECIFICALLY ADDRESS FAN SHUT DOWN IS THIS AREA. | | | 2) IN RESPONSE TO1ST REVIEW COMMENT #8 (AC CONDENSER | | | ANCHORING), THE RESPONSE NARRATIVE IS INDICATING | | | DETAILS ARE FOUND ON SHEET 0793-H-STD-03, HOWEVER THAT | | | SHEET HAS NOT BEEN UPLOADED INTO THE PLAN SET FOR | | | REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|