| 2015-07-16 09:22:43 | 7/16/2015 |
| | PROJECT: COMMERCE PLACE GENERATOR |
| | PERMIT#: 15060516 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) THE RISER DIAGRAM INDICATES A 225AMP BAREAKER IN THE |
| | GENERATOR CONNECTED TO A 3/0 FEEDER TO FEED A 200AMP |
| | RATED ATS. NEITHER THE ATS NOR THE 3/0 FEEDER ARE |
| | APPROVED FOR A 225AMP. REPLACE THE GENERATOR BREAKER |
| | WITH A 200AMP MAX. MANUFACTURER SPEC, PLUS NEC 240.4, |
| | 408.36 |
| | |
| | 2) PROVIDE THE REQUIRED SIGNAGE SHALL BE PLACED AT THE |
| | SERVICE-ENTRANCE EQUIPMENT THAT INDICATES THE TYPE AND |
| | LOCATION OF ON-SITE OPTIONAL STANDBY POWER SOURCES. NEC |
| | 702.8 |
| | |
| | 3) PROVIDE AN ACCURATE GROUNDING ELECTRODE SYSTEM. YOU |
| | HAVE INDICATED IN YOUR NOTES THAT THIS IS A MULTI-UNIT |
| | SERVICE. INDICATE THE SIZE OF THE SERVICE ENTRANCE |
| | CONDUCTORS AND THE APROPRIATE SERVICE GROUNDING |
| | ELECTRODE CONDUCTOR BASED ON NEC 250.66 |
| | |
| | 4) YOU HAVE INDICATED ON THE PANEL SCHEDULE PROVIDED |
| | THAT THERE ARE LOADS TO BE SHED. HOWEVER I DO NOT SEE |
| | ANY LOAD SHED CAPABILITIES IN THE MAUNUFACTURER PRODUCT |
| | DATA SHEETS PROVIDED. NEC 702.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |