| Plan Review Notes For Permit 15060504 |
| Permit Number |
15060504 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-18 17:51:48 | 6751/7501 NORTH JOG ROAD | | | PERMIT #15060504 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | UP: 06/18 DN: 06/29 | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | SEVERAL OF THE TENTS AND TRAILERS APPEAR TO BE LOCATED | | | IN FIRE LANES. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | | ENCLOSURE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|