| Notes |
| Date |
Text |
| 2015-06-12 13:30:16 | 1)SUBMIT A SITE PLAN THAT IS LARGE ENOUGH TO READ WHAT | | | IS BEING PLACED ON THE SITE. WPB AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | 2) INDICATE THE ESTIMATED NUMBER OF ATTENDEES. SANITARY | | | FACILITIES SHALL BE PROVIDED. | | | 3) IF PORTABLE SANITARY FACILITIES ARE BEING PROVIDED | | | SUCH AS A TRAILER AND IT IS CONNECTED TO A SEWAGE | | | HOLDING TANK, INDICATE THE SIZE OF THE HOLDING TANK. A | | | PERMIT FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT MAY | | | BE REQUIRED. SHOW THE LOCATION OF ALL PORTABLE SANITARY | | | FACILITIESFOR THIS EVENT. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 4) IF POTABLE WATER WILL BE CONNECTED ANY PORTABLE | | | RESTROOM UNITS, A BACKFLOW PREVENTION DEVICE SHALL BE | | | INSTALLED ON THE WATER LINE PER THE CITY'S CROSS | | | CONNECTION ORDINANCE.FPC SEC.608. | | | 5) IF NON-POTABLE WATER CONNECTIONS ARE USED, SIGNS | | | SHALL BE POSTED IN CONSPICUOUS PLACES STAING THAT THE | | | WATER IS NON-POTABLE, DO NOT DRINK.FPC 608.8. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|