Plan Review Notes
Plan Review Notes For Permit 15060504
Permit Number 15060504
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-12 12:44:577501 NORTH JOG ROAD
 PERMIT #15060504
 REVIEW COMMENTS - FIRE DEPARTMENT
 UP: 06/18 DN: 06/29
  
 ADDRESS ON PERMIT APPLICATION DOES NOT MATCH THE
 ADDRESS OF THE ACTUAL EVENT; APPEARS TO BE 6751 NORTH
 JOG ROAD - ADMIN BUILDING.
  
 SEPARATE PERMITS ARE NEEDED FOR THE RESTROOM TRAILER
 AND POSSIBLY THE "GAMING" TRAILER IF OCCUPANTS CAN
 ENTER THE STRUCTURE.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 DO ANY OF THE TENTS HAVE SIDEWALLS ON MORE THAN 2
 SIDES?
  
 SEVERAL OF THE TENTS AND TRAILERS APPEAR TO BE LOCATED
 IN FIRE LANES.
  
 ARE THE TABLES/CHAIRS LOCATED BENEATH A TENT (TENT SIZE
 CANNOT BE READ)?
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 WHAT TYPE OF COOKING OPERATIONS ARE TO BE PERFORMED
 UNDER THE FOOD TENT?
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  