2015-06-11 11:42:07APPROVED WITH THE FOLLOWING PROVISOS
 FOR FINAL INSPECTION THE FOLLOWING SHALL BE REQUIRED:
 1. CONDUCTOR INSULATION AS INDICATED ON THE SUBMITTED
 DRAWINGS, DOES NOT COMPLY W/NEC 300.5(B) CORRECT
 ACCORDINGLY.
 2. PANEL SCHEDULE AS PRESENTED INDICATES THE USE OF A
 BACK-FED BREAKER, IF SO, IT SHALL COMPLY W/NEC
 408.36(D).
 3. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES ARE ALLOWED.