Plan Review Notes
Plan Review Notes For Permit 15060423
Permit Number 15060423
Review Stop M
Sequence Number 1
Notes
Date Text
2015-07-27 07:34:031ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060423
  
 1) SHEET M-STD-03 (INCLUSIVE OF ALL PERMIT PLAN SETS
 CONTAINING THIS SHEET): REVISE NOTES #10 & 13
 REFERENCING THE CITY OF TALLAHASSEE FIRE HYDRANT
 COMPLIANCE INFORMATION.
 2) BASED ON THE SOILS REPORT- PIPE BEDDING AND
 DEWATERING GUIDELINES, PLEASE PROVIDE PIPE TRENCH
 CROSS-SECTION DETAILS FOR TYPICAL INSTALLATIONS AND
 HIGH WATER TABLE INSTALLATIONS. INDICATE TRENCH
 DIMENSIONS, PIPE EMBEDMENT DEPTHS, BEDDING MATERIALS
 AND THICKNESSES, COMPACTION AND BACKFILLING
 SPECIFICATIONS.
 3) PROVIDE CIVIL DRAWINGS THAT INCLUDE OVERALL
 UNDERGROUND PIPING LAYOUTS, AND ENLARGED AREA DRAWINGS
 DEPICTING THE UNDERGROUND PIPINGS SPECIFICALLY
 SERVICING EACH TANK, FACILITY, BUILDING, ETC.
 4) SHEETS H-STD-03 &H-STD-04: PLEASE REMOVE THESE
 SHEETS FROM THE PLAN SETS: THEY ARE NOT APPLICABLE TO
 THE THIS PROJECT.
 5) PROVIDE DIMENSIONED SECTION VIEWS AND DETAILS FOR
 THE GUARDRAIL AND HANDRAIL INSTALLATIONS- REFER TO
 SECTION 304.11 FBC-10 MECHANICAL.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR PIPINGS AND
 FITTINGS, AND PIPE INSULATION REVIEWED AND APPROVED BY
 THE DESIGN PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  
  
  