Plan Review Notes
Plan Review Notes For Permit 15060423
Permit Number 15060423
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-06-23 15:11:154395 EASLEY DRIVE - W.A.S STORAGE TANK
 PERMIT #15060423
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-WAS-06: ELECTRICAL ROOMS: PER NFPA 70 ARTICLE
 110.26(C)(3) PERSONNEL DOORS. WHERE CONDUCTORS AND
 EQUIPMENT USED ON CIRCUITS ARE OVER 600 VOLTS OR
 EQUIPMENT IS RATED 1200 A OR MORE THAT CONTAINS
 OVERCURRENT DEVICES, SWITCHING DEVICES, OR CONTROL
 DEVICES IS INSTALLED AND THERE IS A PERSONNEL DOOR(S)
 INTENDED FOR ENTRANCE TO AND EGRESS FROM THE WORKING
 SPACE LESS THAN 25 FEET FROM THE NEAREST EDGE OF THE
 WORKING SPACE, THE DOOR(S) SHALL OPEN IN THE DIRECTION
 OF EGRESS AND BE EQUIPPED WITH PANIC BARS, PRESSURE
 PLATES, OR OTHER DEVICES THAT ARE NORMALLY LATCHED BUT
 OPEN UNDER SIMPLE PRESSURE. CONFIRM CIRCUITS ARE NOT
 OVER 600 VOLTS AND EQUIPMENT IS NOT RATED 1200 A OR
 MORE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved