| 2015-07-14 07:35:08 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060423 WAS STORAGE TANK UPGRADE |
| | ADD: 4395 EASLEY ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | CONTACT: KURT PFEFFER, P. E. |
| | TEL: (561)997-8070 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JULY 14/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTE: SPECIFICATION BOOKS WILL NOT BE REVIEWED AS PART |
| | OF ANY PLAN REVIEW IF SUBMITTED THEY GET STAMPED VOID. |
| | |
| | 1) PLEASE EITHER REMOVE THE INDEX SHEETS 0002-6-GEN.02 |
| | THROUGH 0005-6-GEN.05 OR VOID THEM OUT THEY ARE OF NO |
| | USE TO THIS PROJECT THE WAY IT WAS SUBMITTED. THE PLANS |
| | DO NOT FOLLOW THE INDEX BEING BROUGHT IN BY BUILDING |
| | TYPES. 107.2.1.4 QUALITY OF BUILDING PLANS.THE INDEX |
| | SHOWS 5 ARCHITECTURAL SHEETS WHEREAS IN THIS SUBMITTAL |
| | THERE ARE ONLY 3 SHEETS SUBMITTED? |
| | |
| | 2) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, NOTE |
| | G-3 PLEASE NOTE CORRECT PALM BEACH COUNTY AMENDMENTS, |
| | THE CITY OF WEST PALM BEACH IS UNDER HOME RULE AND THE |
| | CITY HAS ITS OWN CHAPTER 1 AMENDMENTS. 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION. |
| | |
| | 3A) THIS PERMIT WILL REQUIRE A RESIDENT INSPECTOR. |
| | PLEASE REVIEW 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, SECTION 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER INSPECTIONS |
| | SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO |
| | BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION |
| | 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF |
| | RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | 3B) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| | PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| | DEPARTMENT. |
| | FORMS E-MAILED TO: [email protected] THURS. |
| | JULY 02/2015 07:25 AM. |
| | |
| | 3C) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] OR [email protected] |
| | |
| | 3D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] OR [email protected] |
| | |
| | 3E) INFORMATIONAL!!!! NOTE FOR PAPER PLANS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE RESIDENT INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS. |
| | |
| | 3F) INFORMATIONAL!!!!! PLEASE CALL THE CITY OF WEST |
| | PALM BEACHES AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS. NOTE IF INSPECTIONS ARE NOT CALLED |
| | IN, THE PERMIT EXPIRES 6 MONTHS AFTER THE PERMIT |
| | ISSUANCE DATE. A RENEWAL PERMIT WOULD BE REQUIRED AT |
| | THAT POINT. |
| | |
| | 4) SHEET 0241-S GEN-01 GENERAL STRUCTURAL NOTES, HAS A |
| | HEADING FOR FOUNDATION WORK BUT THERE IS NO CRITERIA |
| | LISTED FOR THE SOILS INVESTIGATION REPORT, DATE AND |
| | COMPANY COMPLETING THE SOILS INVESTIGATION. 2010 FBC-B |
| | 1803.5.2. FOUNDATION NOTE F-2 PROVIDES THE ALLOWABLE |
| | SOILS BEARING PRESSURES BUT THERE IS NO DOCUMENTATION |
| | OF A SOILS ANALYSIS AND EVALUATION EVER TAKING PLACE. |
| | |
| | 5) PLEASE NOTE THAT A COPY OF DUNKELBERGER TESTING |
| | REPORT HD145002 APRIL 10, 2014 WAS SUBMITTED BY E-MAIL |
| | FOR REVIEW. THIS REPORT WILL NEED TO EITHER HAVE A HARD |
| | COPY SIGNED AND SEALED OR THE ELECTRONIC PEDDS |
| | SIGNATURE FOR ELECTRONIC VERSIONS OF THIS DOCUMENT. |
| | |
| | 5A) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | VIBRO-COMPACTION FOR THE PROJECT SHOULD BE CARRIED OUT |
| | BY AN EXPERIENCED CONTRACTOR EMPLOYING A GROUND |
| | IMPROVEMENT PLAN THAT HE/SHE PREPARES. THE PLAN SHOULD |
| | UTILIZE CENTER-TO-CENTER SPACING FOR THE |
| | VIBRO-COMPACTION POINTS THAT ARE NORMALLY USED IN |
| | GRANULAR SOILS TO ACHIEVE 80 PERCENT RELATIVE DENSITY. |
| | BEFORE ADOPTION, THE GROUND IMPROVEMENT PLAN SHOULD BE |
| | REVIEWED BY THE GEOTECHNICAL ENGINEER AND STRUCTURAL |
| | ENGINEER FOR CONFORMANCE WITH THE INTENT OF THE |
| | FOUNDATION DESIGN. |
| | PLEASE PROVIDE FOR REVIEW BY THE BUILDING DEPARTMENT |
| | FOR COMPLIANCE. |
| | |
| | 5B) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | RECOMMENDS THE EXCAVATED FILL FOR ALL OF THE DIGESTER |
| | TANKS NOT BE RE-USED, WILL THIS FILL BE USED ELSEWHERE |
| | ON SITE FOR FILL, AND IF SO STORED WHERE, A CONCERN AS |
| | TO THE CLOSENESS OF FILL STORED TO THE EXCAVATION OF |
| | THE DIGESTERS AND OR OTHER STRUCTURES. 2010 FBC-B |
| | 3304.1.2 SURCHARGE & 1808.7 FOUNDATIONS ON OR ADJACENT |
| | TO SLOPES. |
| | |
| | 5C) DUNKELBERGER TESTING REPORT HD145002 APRIL 10, |
| | 2014, PAGE 12 UNDER THE HEADING 9.2 VIBRO-COMPACTION |
| | RECOMMENDS |
| | ADD FILL USED IN THE COMPACTION POINTS SHOULD CONSIST |
| | OF CLEAN SANDS HAVING A SUITABILITY NUMBER (SN) OF 20 |
| | OR LOWER. WE DO NOT BELIEVE THAT THE ON-SITE SANDS WILL |
| | MEET THIS REQUIREMENT. THEREFORE THE ADD FILL WILL NEED |
| | TO BE IMPORTED. PLEASE INCORPORATE INTO THE VIBRO- |
| | FLOTATION PLAN. |
| | |
| | 6) SHEET 0257-S-WAS-10. DETAILS SHOWS A GUARDRAIL |
| | SYSTEM BUT THERE ARE NO DIMENSIONS VERTICALLY SHOWING |
| | COMPLIANCE WITH SECTION 2010 FBC-B 1013.2 HEIGHT. |
| | |
| | 7A) SHEET 0257-S-WAS-10. DETAILS SHOWS A GUARDRAIL |
| | SYSTEM WITH NO VERTICAL DIMENSIONS SHOWING COMPLIANCE |
| | WITH THE 1013.2 HEIGHT. |
| | |
| | 7B) SHEET 0257-S-WAS-10. DETAILS SHOWS A GUARDRAIL |
| | SYSTEM WITH NO VERTICAL DIMENSIONS SHOWING COMPLIANCE |
| | WITH THE 2010 FBC-B 1012.2 HEIGHT REQUIREMENTS. |
| | |
| | 7C) SHEET 0257-S-WAS-10. DETAILS DOES NOT PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1607.7.1 AND 1607.7.1.1. |
| | LOADS ON HANDRAILS AND GUARDS. |
| | |
| | 7D)SHEET 0257-S-WAS-10. DETAILS DOES NOT PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1607.7.1 AND 1607.7.1.1. |
| | LOADS ON HANDRAILS AND GUARDS. |
| | 7E) SHEET 0257-S-WAS-10. DETAILS DOES NOT PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B 1013.2 HEIGHT & 1013.2 |
| | HEIGHT. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |