| Plan Review Notes For Permit 15060421 |
| Permit Number |
15060421 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-13 03:22:14 | 1) BASED ON CITY PLAN REVIEW RECORDS, IT APPEARS THAT A | | | GAS PLAN WAS NOT INCLUDED WITH THE MASTER PERMIT | | | (#15030292). SUBMIT A COPY OF THE FLOOR PLAN SHOWING | | | THE LOCATION OF ALL GAS APPLIANCES.WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1, 107.3.5.3. | | | 2) ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2010 | | | FBCR, SEC. G2404.3. SUBMIT 2 COPIES OF MANUFACTURER'S | | | SPECIFICATION SHEETS FOR ALL GAS APPLIANCES SHOWING THE | | | APPLIANCES COMPLY WITH THE NOTED CODE SECTION. NOTE: | | | PRINTING OF MANUF. SPEC SHEETS FROM THE INTERNET DOES | | | NOT ALWAYS MEET THIS CODE SECTION. | | | 3) INDICATE APPROXIMATE BTU LOAD FOR THE FUTURE GRILL. | | | REFER TO 2010 FBCR, SEC. G2413.2 FOR APPROXIMATE BTU | | | LOAD.INCLUDE THIS IN TOTAL BTU LOAD OF THE SYSTEM. | | | 4) IS THE TANKLESS WATER HEATER ON THE INTERIOR OR | | | EXTEERIOR OF THE STRUCTURE? THE SPECS THAT WERE | | | SUBMITTED ARE FOR AN INDOOR ONLY UNIT. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|