| 2015-10-28 19:02:08 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010 |
| | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS |
| | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. |
| | |
| | 1. CORRECT CONDUCTOR INSULATION NOTE. CONDITIONS AND |
| | NOT SIZING DICTATE CONDUCTOR INSULATION REQUIREMENTS. |
| | 2. FBC-ENERGY CONSERVATION CODE SECTION 502.3.8 |
| | RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND SEALED TO REDUCE |
| | TRANSMISSION OF AIR BETWEEN IT AND THE CEILING SURFACE. |
| | 3. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN |
| | OUTLET BY EVERY PEDESTRIAN ENTRYWAY TO EVERY COMMERCIAL |
| | ESTABLISHMENT. |
| | 4. FBC-E SECTION 505.2.1 REQUIRES THAT LIGHTING BE |
| | INDEPENDENTLY CONTROLLED WITH THE SPACE. |
| | 5. ALL LUMINAIRES ON THE SUSPENDED CEILING SHALL BE |
| | SUPPORTED AS INDICATED IN NEC 410.32. |
| | 6. ALL LUMINAIRE OUTLETS ON WALLS OR CEILINGS SHALL |
| | ABIDE BY THE REQUIREMENTS OF NEC 314.27. |
| | 7. MARK THE LOCATION OF THE RESTROOM, KITCHEN AND ALL |
| | OTHER ROOMS WITHIN THE PREMISES. |
| | 8. PANEL A INDICATES TO BE IN THE HALLWAY, YET THE |
| | FLOOR PLAN SHOWS IT ON THE REA WALL. CORRECT THE |
| | LOCATION ACCORDINGLY AND IF NOT ON THE REAR WALL, |
| | INSTALL THE REQUIRED DISCONNECT FOR THE WATER HEATER AS |
| | INDICATED BY NEC 422.31(B). |
| | 9. PROVIDE SPEC SHEETS FOR ALL PROPOSED EQUIPMENT: |
| | CONDENSING UNITS EXHAUST & SUPPLY FANS AS WELL AS ALL |
| | PERMANENTLY INSTALLED ELECTRICAL EQUIPMENT. |
| | 10. FLOOR PLANS AND EQUIPMENT LAYOUT DIFFERS FROM |
| | SHEETS A-1, E-1 & H-1. CORRECT TO MATCH. |
| | |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. |
| | |
| | WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED BY THE |
| | STANDARD CITY RE-SUBMITTAL FORM. |
| | |
| | PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |