| 2015-09-24 08:59:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15060392 |
| | ADD: 638 BELVEDERE RD. |
| | CONT: EXCEL GENERAL CONSTRUCTION |
| | TEL: (305)984-3488 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. SEPT. 24/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA |
| | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A |
| | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | |
| | |
| | |
| | 1) 2ND REQUEST. SHEET H-1 DOES SHOW ATTACHMENT CURB |
| | DETAILS FOR THE EXHAUST FAN. |
| | |
| | 1A) THERE ARE MULTIPLE TYPE OF FASTENERS PROVIDED ON |
| | THE PLANS WITH THE USE OF THE WORD "OR", THE PLANS NEED |
| | TO BE SPECIFIC TO THE TYPE OF FASTENER. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS |
| | AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE |
| | FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 1B) 2ND REQUET, SEMI-COMPLIED. ENGINEERING SHEETS |
| | ATTACHED PROVIDES THE WIND DESIGN CRITERIA AND ROOF |
| | PRESSURES OF 21.8/ -60.2. THE PRESSURES ARE ASSUMED |
| | VULT? THERE ARE 3 ROOF ZONES, 1,THE CENTER OF THE ROOF, |
| | 2 ZONE THE PERIMETER AND ZONE 3 THE CORNERS OF THE |
| | ROOF. PLEASE ALSO IDENTIFY TO WHICH ROOF ZONE THESE |
| | PRESSURES ARE PROVIDED. NOTE THE ROOF TOP CURBS AND |
| | ROOF TOP EXHAUST FANS AND INTAKE FANS THAT ARE |
| | CONNECTED TO THE HOOD SYSTEM WILL NEED TO SUPPLY THE |
| | PRODUCT APPROVALS FOR THE CURB AND FANS. WE WILL NEED |
| | THE WIND DESIGN CRITERIA CORRECT UNDER THIS PERMIT. THE |
| | PRODUCT APPROVALS CAN BE SUPPLIED WITH THE HOOD PERMIT |
| | AND DESIGN. |
| | |
| | 1C) NEW COMMENT, THERE IS NO INFORMATION AS TO THE ROOF |
| | TOP PENETRATIONS TYPE OF ROOF FRAMING, TYPE OF DECK, |
| | AND IF ADDITIONAL FRAMING WILL BE REQUIRED FOR THE |
| | ANCHORING OF ROOF CURBS AND ROOF TOP A/C STANDS. |
| | 107.2.1.3 COMPONENTS AND CLADDING. |
| | |
| | SHOW COMPLIANCE WITH: WIND DESIGN, A PARTIAL DESIGN IS |
| | GIVEN 170 MPH. WIND DESIGN CRITERIA |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C/ 1609.3 WIND |
| | SPEED CONVERSION |
| | |
| | 1B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 1B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 1C) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES NO APPROVALS |
| | WERE SUBMITTED. |
| | (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP FANS & CURBS. |
| | |
| | THE SUBMITTED A/C STAND PRODUCT APPROVAL IS FROM THE |
| | 2007 FBC UNDER RULE 9B-72 AND IS A COPY. PLEASE NOTE |
| | THIS ADMINISTRATIVE RULE HAS BEEN CHANGED TO 9N-3 NOV. |
| | 01/2010. PLEASE UPDATE THE PRODUCT APPROVAL TO ONE THAT |
| | HAS CURRENT APPROVAL. |
| | |
| | D) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 2) 2ND REQUEST. THE DESIGNER OF RECORD HAS JUST COPIED |
| | THE REQUIREMENTS OF THE CODE SECTIONS LISTED BELOW, NOT |
| | SHOWN COMPLIANCE. 2010 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 1ST REVIEW COMMENT. SHEET A-1 NEEDS TO SHOW COMPLIANCE |
| | WITH 2010 FBC-B 1210.1 AND 1210.2. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |