2015-09-24 08:59:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060392
 ADD: 638 BELVEDERE RD.
 CONT: EXCEL GENERAL CONSTRUCTION
 TEL: (305)984-3488
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 24/2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
  
 1) 2ND REQUEST. SHEET H-1 DOES SHOW ATTACHMENT CURB
 DETAILS FOR THE EXHAUST FAN.
  
 1A) THERE ARE MULTIPLE TYPE OF FASTENERS PROVIDED ON
 THE PLANS WITH THE USE OF THE WORD "OR", THE PLANS NEED
 TO BE SPECIFIC TO THE TYPE OF FASTENER. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 1B) 2ND REQUET, SEMI-COMPLIED. ENGINEERING SHEETS
 ATTACHED PROVIDES THE WIND DESIGN CRITERIA AND ROOF
 PRESSURES OF 21.8/ -60.2. THE PRESSURES ARE ASSUMED
 VULT? THERE ARE 3 ROOF ZONES, 1,THE CENTER OF THE ROOF,
 2 ZONE THE PERIMETER AND ZONE 3 THE CORNERS OF THE
 ROOF. PLEASE ALSO IDENTIFY TO WHICH ROOF ZONE THESE
 PRESSURES ARE PROVIDED. NOTE THE ROOF TOP CURBS AND
 ROOF TOP EXHAUST FANS AND INTAKE FANS THAT ARE
 CONNECTED TO THE HOOD SYSTEM WILL NEED TO SUPPLY THE
 PRODUCT APPROVALS FOR THE CURB AND FANS. WE WILL NEED
 THE WIND DESIGN CRITERIA CORRECT UNDER THIS PERMIT. THE
 PRODUCT APPROVALS CAN BE SUPPLIED WITH THE HOOD PERMIT
 AND DESIGN.
  
 1C) NEW COMMENT, THERE IS NO INFORMATION AS TO THE ROOF
 TOP PENETRATIONS TYPE OF ROOF FRAMING, TYPE OF DECK,
 AND IF ADDITIONAL FRAMING WILL BE REQUIRED FOR THE
 ANCHORING OF ROOF CURBS AND ROOF TOP A/C STANDS.
 107.2.1.3 COMPONENTS AND CLADDING.
  
 SHOW COMPLIANCE WITH: WIND DESIGN, A PARTIAL DESIGN IS
 GIVEN 170 MPH. WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C/ 1609.3 WIND
 SPEED CONVERSION
  
 1B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1C) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES NO APPROVALS
 WERE SUBMITTED.
 (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP FANS & CURBS.
  
 THE SUBMITTED A/C STAND PRODUCT APPROVAL IS FROM THE
 2007 FBC UNDER RULE 9B-72 AND IS A COPY. PLEASE NOTE
 THIS ADMINISTRATIVE RULE HAS BEEN CHANGED TO 9N-3 NOV.
 01/2010. PLEASE UPDATE THE PRODUCT APPROVAL TO ONE THAT
 HAS CURRENT APPROVAL.
  
 D) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2) 2ND REQUEST. THE DESIGNER OF RECORD HAS JUST COPIED
 THE REQUIREMENTS OF THE CODE SECTIONS LISTED BELOW, NOT
 SHOWN COMPLIANCE. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 1ST REVIEW COMMENT. SHEET A-1 NEEDS TO SHOW COMPLIANCE
 WITH 2010 FBC-B 1210.1 AND 1210.2.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  