Plan Review Notes
Plan Review Notes For Permit 15060392
Permit Number 15060392
Review Stop P
Sequence Number 1
Notes
Date Text
2015-07-10 06:51:291) SHT. A-1 - EQUIPMENT SCHEDULE SHOWS ITEM #3 ( WORK
 TABLE) AS GAS BUT THERE IS NO BTU LOAD SHOWN. CLARIFY.
 2) THE SMOKEHOUSE IS SHOWN AS 60,000 BTU'S ON THE GAS
 RISER BUT THE SCHEDULE ON A-1 SHOWS 75,000 BTU'S.
 CLARIFY.
 3) THE RICE COOKER IS SHOWN AS 31,200 BTU'S ON THE
 SCHEDULE BUT THE GAS RISER SHOWS 30,000 BTU'S. CLARIFY.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. THE SPECIFICATIONS SHALL SHOW THAT THE GAS
 EQUIPMENT IS LISTED AND LABELED PER 2010 FBC-FUEL GAS
 SEC.301.3.
 5) INDICATE THE DELIVERY PRESSURE OF THE GAS SYSTEM ON
 THE PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) INDICATE ON THE PLANS THE TYPE OF PIPE BEING
 INSTALLED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 7) SHT. P-1 - SIZE EACH SECTION OF PIPE THAT SUPPLIES
 THE DEEP FRYERS. COMPLY WITH FGC SEC. 402.
 8) THE TOTAL BTU LOAD OF THE APPLIANCES SHOWN ON THE
 EQUIPMENT SCHEDULE DOES NOT CORRELATE WITH THE BTU LOAD
 YOU HAVE SHOWN ON SHT. P-1. CLARIFY.
 9) THERE IS A NOTE ON SHT. P-1 FOR THE GAS THAT READS
 "NAT GAS TB 403 <2>. I HAVE NO IDEA WHAT THIS RELATES
 TO. CLARIFY.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S SPEC SHEETS
 FOR THE TANKLESS WATER HEATER. THE PLANS NOTE THIS AS A
 RESIDENTIAL UNIT.
 11) SEDIMENT TRAPS SHALL BE INSTALLED IN THE GAS LINE
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE PER 2010 FGC
 SEC. 408.4.
 12) SHT. A-1 - LOAD CALCULATION TABLE SHOWS A GREASE
 INTERCEPTOR CALCULATION THAT MAKES NO SENSE. CLARIFY.
 CONCRETE GREASE INTERCEPTORS SHALL COMPLY WITH 2010
 FBC-PLUMBING, TABLE 1003.5.1 FOR SIZING AND
 SECS.1003.3.4 OR F.A.C. 64E-6 AND FPC SEC.1003.5.1,
 1003.5.2 & 1003.5.3. SUBMIT COMPLETE DETAILS FOR THE
 INTERCEPTOR SHOWING CCOMPLIANCE. SUBMIT SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTOR.
 13) SHOW THE LOCATION OF THE GREASE INTERCEPTOR ON THE
 PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) THE INTERCEPTORR SHALL BE EQUIPPED WITH A SAMPLING
 PORT ON THE DISCHARGE LINE. CONTACT KELLY CRANFORD AT
 561-494-1040 IN THE ENGINEERING DEPT.FOR DETAILS.
 15) SUBMIT DETAILS FOR MEANS OF CONTROLLING THERMAL
 EXPANSION WITHIN THE HOT WATER SYSTEM PER 2010 FPC SEC.
 607.3.L
 A THOROUGH REVIEW COULD NOT BE PERFORMED DUE TO THE
 LACK OF SUFFICIENT INFORMATION.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  