| Notes |
| Date |
Text |
| 2015-07-17 09:43:59 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. 2010 FBC-E SECTION 505 HAS MANDATORY LIGHTING | | | REQUIREMENTS WHICH SHALL BE COMPLIED WITH. | | | 2. 2008 NEC 220.88 HAS LOAD CALCULATION REQUIREMENTS | | | FOR NEW RESTAURANTS. PROVIDE LOAD CALCS. | | | 3. 2010 FBC-# 505.5.3 HAS SPECIFIC LIGHT DENSITY | | | REQUIREMENTS WHICH SHALL BE ADHERED TO. | | | 4. 2008 NEC 210.63 REQUIRES A SERVICE OUTLET WITHIN 25' | | | OF HVAC CONDENSING UNITS. PROVIDE A ROOF ELECTRIC | | | DRAWING SHOWING COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|