2015-10-01 09:41:181) RESTROOM #114 SHALL BE HANDICAP ACCESSIBLE PER 2010
 FBC-ACCESSIBILITY, SEC.213.2.
 2) INDICATE ON THE FLOOR PLAN WHICH URINAL IS FOR
 HANDICAP ACCESS. COMPLY W/2010 FAC SECS.213.3.3 & SEC.
 605.
 3) SHT. P-1 - THE GREASE SIZING CALCULATION TABLE
 REFERS TO TABLE 709.1 OF THE FL. PLUMBING CODE. THIS
 TABLE IS NOT TO BE USED FOR SIZING A GREASE
 INTERCEPTOR. REFER TO THE 2010 FPC SEC. 1003.3.4 OR
 TABLE 1003.5.1. THERE IS A NOTE UNDER THE GREASE SIZING
 TABLE THAT IS ON THE PLANS THAT REFERS TO A 4" SANITARY
 BUILDING DRAIN. DELETE THIS NOTE AS IT HAS NO RELEVANCE
 TO THE GREASE WASTE LINE OR CHANGE IT TO READ "GREASE
 BUILDING DRAIN PIPE=4".
 4) THE GRAVITY GREASE INTERCEPTOR SHALL COMPLY WITH THE
 LATEST VERSION OF THE CITY OF WEST PALM BEACH
 ENGINEERING DEPT. DETAIL AND FL. ADMIN. CODE RULE 64E-6
 . CONTACT KELLY CRANFORD AT 561-835-7243.
 5) SHT.P-2 - SIZE ALL SECTIONS OF THE VENTS ON THE
 SANITARY RISER .WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 THIS IS THE SECOND REQUEST FOR THE ABOVE ITEMS.
  