| Plan Review Notes For Permit 15060362 |
| Permit Number |
15060362 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-01 10:19:00 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS | | | LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3. | | | 2) SHT. P-2 - "COMBUSTION AIR REQUIREMENTS" NOTE AT | | | BOTTOM OF BOX READS "PROVIDED 5902 CFM FROM HOOD SUPPLY | | | FANS." THE HOOD SUPPLY FANS CANNOT BE USED TO SUPPLY | | | COMBUSTION AIR FOR THE APPLIANCES.REFER TO THE 2010 | | | FBC- MECHANICAL SEC.508. THE MAKEUP AIR IS DEDICATED TO | | | THE EXHAUST SYSTEM FOR THE KITCHEN. | | | 3) I AM THOROUGHLY CONFUSED AS TO YOUR CALCULATIONS FOR | | | COMBUSTION AIR ON SHEET P-2. YOU SHOW A GAS INPUT OF | | | 451,000. HOW DID YOU ARRIVE AT THIS NUMBER? THE GAS | | | CODE NO LONGER REFERS TO "CONFINED" & "UNCONFINED" | | | SPACES. COMBUSTION AIR SHALL BE PROVIDED IN ACCORDANCE | | | WITH THE 2010 FBC-FUEL GAS SEC.304.1. | | | I DO NOT UNDERSTAND YOUR EQUATION FOR THE COMBUSTION | | | AIR REQUIRED (18CFM X TOT BTUH/100,000). PLEASE | | | EXPLAIN. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|