Plan Review Notes
Plan Review Notes For Permit 15060362
Permit Number 15060362
Review Stop G
Sequence Number 2
Notes
Date Text
2015-10-01 10:19:001) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS
 LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3.
 2) SHT. P-2 - "COMBUSTION AIR REQUIREMENTS" NOTE AT
 BOTTOM OF BOX READS "PROVIDED 5902 CFM FROM HOOD SUPPLY
 FANS." THE HOOD SUPPLY FANS CANNOT BE USED TO SUPPLY
 COMBUSTION AIR FOR THE APPLIANCES.REFER TO THE 2010
 FBC- MECHANICAL SEC.508. THE MAKEUP AIR IS DEDICATED TO
 THE EXHAUST SYSTEM FOR THE KITCHEN.
 3) I AM THOROUGHLY CONFUSED AS TO YOUR CALCULATIONS FOR
 COMBUSTION AIR ON SHEET P-2. YOU SHOW A GAS INPUT OF
 451,000. HOW DID YOU ARRIVE AT THIS NUMBER? THE GAS
 CODE NO LONGER REFERS TO "CONFINED" & "UNCONFINED"
 SPACES. COMBUSTION AIR SHALL BE PROVIDED IN ACCORDANCE
 WITH THE 2010 FBC-FUEL GAS SEC.304.1.
 I DO NOT UNDERSTAND YOUR EQUATION FOR THE COMBUSTION
 AIR REQUIRED (18CFM X TOT BTUH/100,000). PLEASE
 EXPLAIN.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  