| 2015-07-10 13:36:21 | 1) THE WOMEN'S RESTROOM SHALL HAVE THE SAME NUMBER OF |
| | WATER CLOSETS AS THE COMBINED TOTAL OF WATER CLOSETS |
| | AND URINALS FOR THE MEN. 2010 FBC-PLUMBING, SEC.403.1.3 |
| | (EXCEPTION). |
| | 2) RESTROOM #114 SHALL BE HANDICAP ACCESSIBLE PER 2010 |
| | FBC-ACCESSIBILITY, SEC.213.2. |
| | 3) INDICATE ON THE FLOOR PLAN WHICH URINAL IS FOR |
| | HANDICAP ACCESS. COMPLY W/2010 FAC SECS.213.3.3 & SEC. |
| | 605. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS |
| | LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3. |
| | 5) SHT. A-3 IS ILLEGIBLE. SUBMIT A NEW SHEET THAT IS |
| | CLEAR IN DETAIL.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 6) SHT. P-1 - THE GREASE SIZING CALCULATION TABLE |
| | REFERS TO TABLE 709.1 OF THE FL. PLUMBING CODE. THIS |
| | TABLE IS NOT TO BE USED FOR SIZING A GREASE |
| | INTERCEPTOR. REFER TO THE 2010 FPC SEC. 1003.3.4 OR |
| | TABLE 1003.5.1. THERE IS A NOTE UNDER THE GREASE SIZING |
| | TABLE THAT IS ON THE PLANS THAT REFERS TO A 4" SANITARY |
| | BUILDING DRAIN. DELETE THIS NOTE AS IT HAS NO RELEVANCE |
| | TO THE GREASE WASTE LINE OR CHANGE IT TO READ "GREASE |
| | BUILDING DRAIN PIPE=4". |
| | 7) THE GRAVITY GREASE INTERCEPTOR SHALL COMPLY WITH THE |
| | LATEST VERSION OF THE CITY OF WEST PALM BEACH |
| | ENGINEERING DEPT. DETAIL AND FL. ADMIN. CODE RULE 64E-6 |
| | . CONTACT KELLY CRANFORD AT 561-835-7243. |
| | 8) SHT.P-2 - SIZE ALL SECTIONS OF THE VENTS ON THE |
| | SANITARY RISER .WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 9) THE BTU LOAD OF THE GAS APPLIANCES SHOWN ON THE |
| | KITCHEN EQUIPMENT SCHEDULE ON A-3.0 DOES NOT MATCH THE |
| | BTU LOAD SHOWN ON THE GAS RISER ON SHT.P-2. CLARIFY. |
| | 10) A 96,000 BTU GAS FIRED TILT SKILLET IS SHOWN ON THE |
| | EQUIPMENT SCHEDULE ON A-3.0 BUT NOT ON THE GAS RISER. |
| | CLARIFY. |
| | 11) THE TOTAL BTU LOAD FOR THE LOW PRESSURE COOKLINE IS |
| | CALCULATED AS 771,500 BTU'S. SHOW THE TOTAL DEVELOPED |
| | LENGTH DISTANCE FROM THE LOW PRESSURE REGULATOR TO THE |
| | FURTHEST OUTLET ON THE COOKLINE ( FRYER ). SIZE THIS |
| | SECTION OF PIPING IN ACCORDANCE WITH TABLE 402.4 (2).. |
| | 12) SEDIMENT TRAPS SHALL BE INSTALLED AT EACH APPLIANCE |
| | AND SHALL BE INSTALLED DOWNSTREAM OF THE APPLIANCE |
| | SHUTOFF VALVE AS CLOSE TO THE INLET OF THE APPLIANCE AS |
| | PRACTICAL. 2010 FGC SEC.408.4. |
| | 13) MY CALCULATIONS FOR THE TOTAL BTU LOAD ON THE |
| | SYSTEM IS 1,014,500 BTU'S. PLEASE RECHECK YOUR |
| | CALCULATIONS FOR THE THE TOTAL BTU LOAD AND REVISE THE |
| | LOAD ON THE PLANS. |
| | 14) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES PER 2010 FBC-FUEL GAS, SEC.304. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |