2015-06-26 17:14:391ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060362
  
 1) THE CITY OF WPB BUILDING DEPT. REQUIRES SEPARATE
 PERMIT APPLICATIONS AND PLAN SUBMITTALS FOR KITCHEN
 HOODS AND FIRE SUPPRESSION, FIRE SPRINKLERS, AND
 WALK-IN COOLERS AND FREEZERS. PLACE NOTES ON THE PLAN
 TO INDICATE COMPLIANCE.
 2) THE O/A CALCULATION ON SHEET M-1 DOES NOT INCLUDE
 THE LOBBY AND OFFICE AREAS, AND THE CALCULATION FOR THE
 DINING ROOM SHOULD BE BASED ON THE 213 OCCUPANT LOAD OR
 THE DEFAULT DENSITY LOAD IN TABLE 403.3 FBC-10
 MECHANICAL: PLEASE REVISE.
 3) PROVIDE AN AIR BALANCE CALCULATION ON SHEET M-1.
 4) M-2 PROVIDE THE WIND DESIGN CRITERIA AND DESIGN
 PRESSURES FOR TIE-DOWN OF THE CONDENSER UNITS- SECTION
 301.12 FBC-10 MECHANICAL.
 5) THE SUBMITTED ENERGY EFFICIENCY FORM 502-2010 IS
 LISTING NO VALUES FOR ENVELOPE COMPONENTS- REFERENCE
 TABLE 101.4.1 FBC-10 ENERGY CONSERVATION. PER THE
 TABLE, PREVIOUSLY UNCONDITIONED SPACES OR CHANGES OF
 OCCUPANCY REQUIRE COMPLIANCE WITH THE CURRENT CODE,
 INCLUDING THE THERMAL ENVELOPE COMPONENTS- REFERENCE
 SECTION 502.
 6) HOOD PLANS: ALTHOUGH THESE PLANS ARE NOT UNDER
 REVIEW AT THIS TIME, PLEASE REFERENCE SECTIONS 401.4,
 506.3.12.2, & 506.3.12.3 FOR AIR INTAKE AND EXHAUST
 TERMINATION LOCATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER