| Date |
Text |
| 2015-06-26 17:14:39 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | PERMIT #15060362 |
| | |
| | 1) THE CITY OF WPB BUILDING DEPT. REQUIRES SEPARATE |
| | PERMIT APPLICATIONS AND PLAN SUBMITTALS FOR KITCHEN |
| | HOODS AND FIRE SUPPRESSION, FIRE SPRINKLERS, AND |
| | WALK-IN COOLERS AND FREEZERS. PLACE NOTES ON THE PLAN |
| | TO INDICATE COMPLIANCE. |
| | 2) THE O/A CALCULATION ON SHEET M-1 DOES NOT INCLUDE |
| | THE LOBBY AND OFFICE AREAS, AND THE CALCULATION FOR THE |
| | DINING ROOM SHOULD BE BASED ON THE 213 OCCUPANT LOAD OR |
| | THE DEFAULT DENSITY LOAD IN TABLE 403.3 FBC-10 |
| | MECHANICAL: PLEASE REVISE. |
| | 3) PROVIDE AN AIR BALANCE CALCULATION ON SHEET M-1. |
| | 4) M-2 PROVIDE THE WIND DESIGN CRITERIA AND DESIGN |
| | PRESSURES FOR TIE-DOWN OF THE CONDENSER UNITS- SECTION |
| | 301.12 FBC-10 MECHANICAL. |
| | 5) THE SUBMITTED ENERGY EFFICIENCY FORM 502-2010 IS |
| | LISTING NO VALUES FOR ENVELOPE COMPONENTS- REFERENCE |
| | TABLE 101.4.1 FBC-10 ENERGY CONSERVATION. PER THE |
| | TABLE, PREVIOUSLY UNCONDITIONED SPACES OR CHANGES OF |
| | OCCUPANCY REQUIRE COMPLIANCE WITH THE CURRENT CODE, |
| | INCLUDING THE THERMAL ENVELOPE COMPONENTS- REFERENCE |
| | SECTION 502. |
| | 6) HOOD PLANS: ALTHOUGH THESE PLANS ARE NOT UNDER |
| | REVIEW AT THIS TIME, PLEASE REFERENCE SECTIONS 401.4, |
| | 506.3.12.2, & 506.3.12.3 FOR AIR INTAKE AND EXHAUST |
| | TERMINATION LOCATIONS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |