Plan Review Notes
Plan Review Notes For Permit 15060362
Permit Number 15060362
Review Stop G
Sequence Number 1
Notes
Date Text
2015-07-11 04:54:481) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS
 LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3.
 2) THE BTU LOAD OF THE GAS APPLIANCES SHOWN ON THE
 KITCHEN EQUIPMENT SCHEDULE ON A-3.0 DOES NOT MATCH THE
 BTU LOAD SHOWN ON THE GAS RISER ON SHT.P-2. CLARIFY.
 3) A 96,000 BTU GAS FIRED TILT SKILLET IS SHOWN ON THE
 EQUIPMENT SCHEDULE ON A-3.0 BUT NOT ON THE GAS RISER.
 CLARIFY.
 4) THE TOTAL BTU LOAD FOR THE LOW PRESSURE COOKLINE IS
 CALCULATED AS 771,500 BTU'S. SHOW THE TOTAL DEVELOPED
 LENGTH DISTANCE FROM THE LOW PRESSURE REGULATOR TO THE
 FURTHEST OUTLET ON THE COOKLINE ( FRYER ). SIZE THIS
 SECTION OF PIPING IN ACCORDANCE WITH TABLE 402.4 (2)..
 5) SEDIMENT TRAPS SHALL BE INSTALLED AT EACH APPLIANCE
 AND SHALL BE INSTALLED DOWNSTREAM OF THE APPLIANCE
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE APPLIANCE AS
 PRACTICAL. 2010 FGC SEC.408.4.
 6) MY CALCULATIONS FOR THE TOTAL BTU LOAD ON THE SYSTEM
 IS 1,014,500 BTU'S. PLEASE RECHECK YOUR CALCULATIONS
 FOR THE THE TOTAL BTU LOAD AND REVISE THE LOAD ON THE
 PLANS.
 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES PER 2010 FBC-FUEL GAS, SEC.304.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  