| 2015-07-11 04:54:48 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT. SPECS SHALL SHOW THAT THE EQUIPMENT IS | | | LISTED AND LABELED PER 201 FUEL GAS CODE SEC.301.3. | | | 2) THE BTU LOAD OF THE GAS APPLIANCES SHOWN ON THE | | | KITCHEN EQUIPMENT SCHEDULE ON A-3.0 DOES NOT MATCH THE | | | BTU LOAD SHOWN ON THE GAS RISER ON SHT.P-2. CLARIFY. | | | 3) A 96,000 BTU GAS FIRED TILT SKILLET IS SHOWN ON THE | | | EQUIPMENT SCHEDULE ON A-3.0 BUT NOT ON THE GAS RISER. | | | CLARIFY. | | | 4) THE TOTAL BTU LOAD FOR THE LOW PRESSURE COOKLINE IS | | | CALCULATED AS 771,500 BTU'S. SHOW THE TOTAL DEVELOPED | | | LENGTH DISTANCE FROM THE LOW PRESSURE REGULATOR TO THE | | | FURTHEST OUTLET ON THE COOKLINE ( FRYER ). SIZE THIS | | | SECTION OF PIPING IN ACCORDANCE WITH TABLE 402.4 (2).. | | | 5) SEDIMENT TRAPS SHALL BE INSTALLED AT EACH APPLIANCE | | | AND SHALL BE INSTALLED DOWNSTREAM OF THE APPLIANCE | | | SHUTOFF VALVE AS CLOSE TO THE INLET OF THE APPLIANCE AS | | | PRACTICAL. 2010 FGC SEC.408.4. | | | 6) MY CALCULATIONS FOR THE TOTAL BTU LOAD ON THE SYSTEM | | | IS 1,014,500 BTU'S. PLEASE RECHECK YOUR CALCULATIONS | | | FOR THE THE TOTAL BTU LOAD AND REVISE THE LOAD ON THE | | | PLANS. | | | 7) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS | | | APPLIANCES PER 2010 FBC-FUEL GAS, SEC.304. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|