| 2015-07-21 19:35:35 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | 1. NEC 600.5 REQUIRES THAT THERE BE A SIGN OUTLET BY |
| | EVERY ENTRANCE, EXCEPT SERVICE HALLWAYS AND CORRIDORS. |
| | 2. NEC 300.7 REQUIRES THAT RACEWAYS EXPOSED TO |
| | DIFFERENT TEMPERATURES BE SEALED TO PREVENT THE |
| | TRANSFER OF WARN AIR INTO THE COLD ENVIRONMENT. |
| | 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS ON ALL |
| | PANEL OTHER THAN IN DWELLING UNITS. |
| | 4 NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT |
| | ELECTRICAL EQUIPMENT. SUCH IS NOT INDICATED FOR |
| | EQUIPMENT/MECHANICAL ROOM 116. |
| | 5. FBC-B 1006.2.1 EMERGENCY LIGHTING MAY BE REQUIRED |
| | INSIDE THE WALK IN COOLERS AND FREEZERS. |
| | 6. THE EQUIPMENT/MECHANICAL ROOM 116 REFLECTS A DOOR |
| | ONLY IN THE ELECTRICAL PAGES, BUT NOT ON ANY OF THE "A" |
| | SHEETS. CORRECT THIS TO INDICATE THE PROPER DOOR AND |
| | SWING. |
| | 7. PROVIDE A ROOF ELECTRICAL SHEET INDICATING THE |
| | LOCATION OF ALL ELECTRICAL EQUIPMENT INSTALLED ON THE |
| | ROOF. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |