2015-07-21 19:35:35PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. NEC 600.5 REQUIRES THAT THERE BE A SIGN OUTLET BY
 EVERY ENTRANCE, EXCEPT SERVICE HALLWAYS AND CORRIDORS.
 2. NEC 300.7 REQUIRES THAT RACEWAYS EXPOSED TO
 DIFFERENT TEMPERATURES BE SEALED TO PREVENT THE
 TRANSFER OF WARN AIR INTO THE COLD ENVIRONMENT.
 3. NEC 110.16 REQUIRES ARC-FLASH WARNING LABELS ON ALL
 PANEL OTHER THAN IN DWELLING UNITS.
 4 NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT
 ELECTRICAL EQUIPMENT. SUCH IS NOT INDICATED FOR
 EQUIPMENT/MECHANICAL ROOM 116.
 5. FBC-B 1006.2.1 EMERGENCY LIGHTING MAY BE REQUIRED
 INSIDE THE WALK IN COOLERS AND FREEZERS.
 6. THE EQUIPMENT/MECHANICAL ROOM 116 REFLECTS A DOOR
 ONLY IN THE ELECTRICAL PAGES, BUT NOT ON ANY OF THE "A"
 SHEETS. CORRECT THIS TO INDICATE THE PROPER DOOR AND
 SWING.
 7. PROVIDE A ROOF ELECTRICAL SHEET INDICATING THE
 LOCATION OF ALL ELECTRICAL EQUIPMENT INSTALLED ON THE
 ROOF.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  