2016-01-25 16:56:213RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060341
 1/25/16
  
 1) PLEASE PROVIDE AN MSDS SHEET FOR THE CHEMO, AND
 REFER TO SECTION 510 HAZARDOUS EXHAUST SYSTEMS. IF THE
 MATERIAL STORED OR DISPENSED IN THE ROOM MEETS ANY OF
 THE THREE CONDITIONS LISTED UNDER 510.2 THEN AN
 INDEPENDENT HAZARDOUS EXHAUST SYSTEM, NOT CONNECTED
 WITH THE TRASH ROOM AND DRUG STORAGE, SHALL BE
 INSTALLED.
 2) PROVIDE VENTILATION CALCULATIONS FOR THE TRASH,
 CHEMO, AND DRUG STORAGE ROOMS- SEE TABLE 403.3, AND
 ALSO ASHRAE 170-2008.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER