Plan Review Notes
Plan Review Notes For Permit 15060341
Permit Number 15060341
Review Stop M
Sequence Number 2
Notes
Date Text
2015-11-10 12:10:462ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060341
 11/10/15
  
 1) SHEET M3.1 WHICH IS SHOWING THE "NEW FAN SCHEDULE"
 WAS NOT INCLUDED WITH THE REVISED PLANS SETS. PLEASE
 PROVIDE THE SHEET AND CLARIFY WHICH FAN IS THE NEW
 TRASH ROOM FAN (SEE NOTE #9 ON SHEET A2.43).
 2) PLACE A TARGET NOTE ON THE VARIOUS FLOOR PLAN
 DRAWINGS TO INDICATE THE LOCATION OF THE NEW EXHAUST
 CHASE.
 3) M3.2: AS PREVIOUSLY REQUESTED IN COMMENT #1 FROM THE
 1ST REVIEW ABOUT THE ROOF DUCT SUPPORT DETAIL "INDICATE
 THE TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO
 ATTACH THE STRAPS TO THE STAND, AND THE STAND BASE
 PLATES TO THE ROOF STRUCTURE".
 4) M3.2: THERE IS NO DETAIL FOR ATTACHMENT OF THE
 EXHAUST FAN EQUIPMENT CURB TO THE ROOF STRUCTURE-
 EITHER ON THE PLAN- OR IN THE GREENHECK FAN NOA. IS
 THERE A SEPARATE NOA FOR THIS PRODUCT?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  