| Plan Review Notes For Permit 15060341 |
| Permit Number |
15060341 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-10 12:10:46 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15060341 | | | 11/10/15 | | | | | | 1) SHEET M3.1 WHICH IS SHOWING THE "NEW FAN SCHEDULE" | | | WAS NOT INCLUDED WITH THE REVISED PLANS SETS. PLEASE | | | PROVIDE THE SHEET AND CLARIFY WHICH FAN IS THE NEW | | | TRASH ROOM FAN (SEE NOTE #9 ON SHEET A2.43). | | | 2) PLACE A TARGET NOTE ON THE VARIOUS FLOOR PLAN | | | DRAWINGS TO INDICATE THE LOCATION OF THE NEW EXHAUST | | | CHASE. | | | 3) M3.2: AS PREVIOUSLY REQUESTED IN COMMENT #1 FROM THE | | | 1ST REVIEW ABOUT THE ROOF DUCT SUPPORT DETAIL "INDICATE | | | THE TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO | | | ATTACH THE STRAPS TO THE STAND, AND THE STAND BASE | | | PLATES TO THE ROOF STRUCTURE". | | | 4) M3.2: THERE IS NO DETAIL FOR ATTACHMENT OF THE | | | EXHAUST FAN EQUIPMENT CURB TO THE ROOF STRUCTURE- | | | EITHER ON THE PLAN- OR IN THE GREENHECK FAN NOA. IS | | | THERE A SEPARATE NOA FOR THIS PRODUCT? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|