Plan Review Notes
Plan Review Notes For Permit 15060341
Permit Number 15060341
Review Stop B
Sequence Number 2
Notes
Date Text
2015-11-14 10:26:35BUILDING PLAN REVIEW
 W. P. B. REVISION: 15060341
 W. P. B. PERMIT: 14120225
 ADD: 1309 N. FLAGLER
 CONT: WESTBROOKE
 TEL: (561)239-7133
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 14/ 2015
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SHEET A2.24 NOT UPDATED, SHOW A
 PRIVATE OFFICE TB#248B WITH 2 DOORS IN SERIES. PLEASE
 SEE THE 2010 FBC-ACCESSIBLITY CODE 404.2.6 DOORS IN
 SERIES.
  
 2) 2ND REQUEST SHEET A2.41, A2.A2.42 & A2.44ALL SHOW A
 STORAGE ROOM # TB254 AND THE DOORWAY TO THE LEFT (LEADS
 INTO THE CORRIDOR) DOES NOT COMPLY WITH SECTION FROM
 THE 2010 FBC-ACCESSIBLITY CODE 404.2.4 AND FIGURE
 404.2.4.1(A). MANEUVERING CLEARANCES.
  
 3) 2ND REQUEST. SEMI-COMPLIED. A MIAMI-DADE NOA
 14-0325.06 GREENHECK FAN PRODUCT APPROVAL WAS SUBMITED.
 PLEASE PROVIDE WHERE IN THE MECHANICAL SHEETS THE MODEL
 (SERIES) OF THE EXHAUST FAN TO BE INSTALLED ON THE
 ROOF. THE PRODUCT APPROVAL IS VERY SPECIFIC TO WHICH
 UNITS ARE COVERED UNDER THIS APPROVAL. THE MODEL/
 SERIES ON THE MECHANICAL SHEETS WILL NEED TO MATCH ONE
 LISTED WITHIN THE NOA APPROVAL. THE PRESSURES FOR THIS
 NOA ARE GOOD FOR +/-90 PSF.
  
 ROOF TOP STAND NOA 09-0804.05 PLEASE SEE THE TECHNICAL
 SHEET 2 PLEASE IDENTIFY WHICH STAND WILL BE INSTALLED
 ON THIS JOBSITE, WXDXH AND MAXIMUM STAND HEIGHT, AND
 MIN. CLEAR HEIGHT, THIS WILL PROVIDE WITH THE TYPE
 ANCHOR A AND THE MAXIMUM ALLOWABLE PRESSURES TO BE USED
 WITH THIS STAND.
  
 1ST REVIEW COMMENT. SHEET M3.2 DETAIL # 1 SHOWS ROOF
 TOP EQUIPMENT, EXHAUST FAN AND CURB. THE PLAN DETAIL
 REQUIRES A NOA, A MIAMI-DADE NOTICE OF ACCEPTANCE
 REPORT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS, CURBS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/ C STANDS
  
 4) SEMI-COMPLIED, ADDTIONAL INFORMATION IS EQUIRED FROM
 THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS
 PROJECT. 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4.1)COMPLIED. THE BASIC WIND SPEED, VU, SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10 180
 VULT.
  
 4.2) COMPLIED. AN IMPORTANCE FACTOR, FIGURE 1609 A-C,
 ASCE 7-10. BUILD. CAT. III
  
 4.3) COMPLIED. AN EXPOSURE CATEGORY SHALL BE DETERMINED
 IN ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) NOT COMPLIED, 2ND REQUEST, DEIGN PRESSURES FOR
 ROOF TOP EQUIPMENT NOT GIVEN. A HEIGHT AND EXPOSURE
 ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED FROM
 TABLE 1609.7.2. ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP
 10 FEET ABOVE THE ROOF DECK LOCATED AT 69 FEET S101.
 EXPOSURE C/ 180 MPH.
  
 4.5) NOT COMPLIED, 2ND REQUEST, COMPONENTS & CLADDING
 PRESSURES POSITIVE & NEGATIVE TABLE 1609.2(2) ABOVE 60
 FEET ASCE 7-10. ROOF TOP EQUIPMENT STICKS UP 10 FEET
 ABOVE THE ROOF DECK LOCATED AT 69 FEET S101. EXPOSURE
 C/ 180 MPH.
  
  
 5) 2ND EQUEST. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 1609.8 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 6) SEMI-COMPLIED. SHEET S101 SHOWS A DETAIL FOR GUY
 WIRES BUT IS MISSING THE TOP CONNECTION TO THE
 GALVANIZED L 2X2X 1/4 WELDED ANGLE FRAME. SHEET M3.2
 DETAIL # 1. PLEASE PROVIDE ENGINEERING FOR THE GUY
 WIRES FOR THE ROOF TOP EXHAUST FAN DEPICTED. SHOW THE
 WIRE GAUGE,
 HOW THE GUY WIRE WILL BE SECURED AT EACH END, WHAT WILL
 THE GUY WIRE BE FASTENED TOO AND TYPE OF FASTENERS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  