Plan Review Notes
Plan Review Notes For Permit 15060341
Permit Number 15060341
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-29 09:00:251ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE REVISED PLANS DO NOT INDICATE THE AHCA REQUESTED
 COMPLIANCE INFORMATION AND WIND LOAD ANCHORING DETAILS
 FOR HVAC EQUIPMENT HAVE BEEN PROVIDED. PLEASE REVIEW
 SECTION 419.4.2.6.1 AND 1609.1 FBC-10 BUILDING. THE
 ENGINERER OF RECORD SHALL PROVIDE THE WIND LOAD DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLANS. ALL
 REQUIRED NOA'S SHALL BE REVIEWED BY THE EOR AND ALL
 APPLICABLE DETAILS, NOTES, AND DESIGN PRESSURES ON THE
 DOCUMENTS SHALL HAVE IDENTIFYING MARKS, CIRCLES, OR
 HIGHLIGHTS. REFERENCE SHEET M3.2 DETAIL 1- A) INDICATE
 HOW THE GUY WIRES ARE ATTACHING TO THE EXHAUST DUCT AND
 TO THE ROOF. B) INDICATE HOW THE FAN UNIT IS ATTACHING
 TO THE STAND, AND HOW THE STAND IS ATTACHED TO THE
 ROOF. C) INDICATE THE NOA NUMBER FOR THE ROOF STAND.
 REFERENCE M3.2 DETAIL 4- A) PROVIDE THE GAGE OF STEEL
 FOR THE DUCT SUPPORT AND DUCT STRAP. B) INDICATE THE
 TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO ATTACH
 THE STRAPS TO THE STAND, AND THE STAND BASE PLATES TO
 THE ROOF STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  