| 2015-06-29 09:00:25 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) THE REVISED PLANS DO NOT INDICATE THE AHCA REQUESTED | | | COMPLIANCE INFORMATION AND WIND LOAD ANCHORING DETAILS | | | FOR HVAC EQUIPMENT HAVE BEEN PROVIDED. PLEASE REVIEW | | | SECTION 419.4.2.6.1 AND 1609.1 FBC-10 BUILDING. THE | | | ENGINERER OF RECORD SHALL PROVIDE THE WIND LOAD DESIGN | | | CRITERIA AND DESIGN PRESSURES ON THE PLANS. ALL | | | REQUIRED NOA'S SHALL BE REVIEWED BY THE EOR AND ALL | | | APPLICABLE DETAILS, NOTES, AND DESIGN PRESSURES ON THE | | | DOCUMENTS SHALL HAVE IDENTIFYING MARKS, CIRCLES, OR | | | HIGHLIGHTS. REFERENCE SHEET M3.2 DETAIL 1- A) INDICATE | | | HOW THE GUY WIRES ARE ATTACHING TO THE EXHAUST DUCT AND | | | TO THE ROOF. B) INDICATE HOW THE FAN UNIT IS ATTACHING | | | TO THE STAND, AND HOW THE STAND IS ATTACHED TO THE | | | ROOF. C) INDICATE THE NOA NUMBER FOR THE ROOF STAND. | | | REFERENCE M3.2 DETAIL 4- A) PROVIDE THE GAGE OF STEEL | | | FOR THE DUCT SUPPORT AND DUCT STRAP. B) INDICATE THE | | | TYPE AND SIZE OF ANCHOR BOLTS OR FASTENERS TO ATTACH | | | THE STRAPS TO THE STAND, AND THE STAND BASE PLATES TO | | | THE ROOF STRUCTURE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|