| 2015-09-01 15:36:03 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THE FIRE ALARM REQUIRES A SEPARATE SUBMITTAL AND | | | SHOP DRAWINGS. | | | 2. PAGE "A1.01" IDENTIFIED THE AREA OF WORK, BUT THAT | | | AREA IS NOT CLEARLY DEFINED ON THE ELECTRICAL SHEETS. | | | 3. THE ELECTRICAL METER ROOMS AND ADJACENT AREA APPEAR | | | TO BE OUTSIDE OF THE AREA OF WORK AS DESCRIBED ON A1.01 | | | 4. LIGHTING CONTROLS DO NOT APPEAR TO BE WITHIN THE | | | FBC-E GUIDELINES. | | | 5. YOU SHALL SUBMIT THE ELECTRICAL RISER DIAGRAM WITH | | | THE RESPECTIVE ELECTRICAL LOAD CALCS. | | | 6. YOU SHALL PROVIDE A CIRCUIT IDENTIFICATION SHEET | | | (PANEL SCHEDULE) | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|