2015-09-01 15:36:03PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FIRE ALARM REQUIRES A SEPARATE SUBMITTAL AND
 SHOP DRAWINGS.
 2. PAGE "A1.01" IDENTIFIED THE AREA OF WORK, BUT THAT
 AREA IS NOT CLEARLY DEFINED ON THE ELECTRICAL SHEETS.
 3. THE ELECTRICAL METER ROOMS AND ADJACENT AREA APPEAR
 TO BE OUTSIDE OF THE AREA OF WORK AS DESCRIBED ON A1.01
 4. LIGHTING CONTROLS DO NOT APPEAR TO BE WITHIN THE
 FBC-E GUIDELINES.
 5. YOU SHALL SUBMIT THE ELECTRICAL RISER DIAGRAM WITH
 THE RESPECTIVE ELECTRICAL LOAD CALCS.
 6. YOU SHALL PROVIDE A CIRCUIT IDENTIFICATION SHEET
 (PANEL SCHEDULE)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  