| 2015-06-29 13:57:17 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15060341 |
| | W. P. B. PERMIT: 14120225 |
| | ADD: 1309 N. FLAGLER |
| | CONT: WESTBROOKE |
| | TEL: (561)239-7133 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 29/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEETS A2.22 & A2.24 SHEETS SHOW A PRIVATE OFFICE |
| | TB#248B WITH 2 DOORS IN SERIES. PLEASE SEE THE 2010 |
| | FBC-ACCESSIBLITY CODE 404.2.6 DOORS IN SERIES. |
| | |
| | 2) SHEET A2.41, A2.A2.42 & A2.44ALL SHOW A STORAGE ROOM |
| | # TB254 AND THE DOORWAY TO THE LEFT DOES NOT COMPLY |
| | WITH SECTION FROM THE 2010 FBC-ACCESSIBLITY CODE |
| | 404.2.4 AND FIGURE 404.2.4.1(A). MANEUVERING |
| | CLEARANCES. |
| | |
| | 3) SHEET M3.2 DETAIL # 1 SHOWS ROOF TOP EQUIPMENT, |
| | EXHAUST FAN AND CURB. THE PLAN DETAIL REQUIRES A NOA, A |
| | MIAMI-DADE NOTICE OF ACCEPTANCE REPORT. 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS, CURBS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/ C STANDS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS |
| | PROJECT. 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 180 VULT. |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | BUILD. CAT. III |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) |
| | |
| | 5) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1609.8 |
| | ROOFTOP STRUCTURES AND EQUIPMENT. |
| | |
| | 6) SHEET M3.2 DETAIL # 1. PLEASE PROVIDE ENGINEERING |
| | FOR THE GUY WIRES FOR THE ROOF TOP EXHAUST FAN |
| | DEPICTED. SHOW THE WIRE GAUGE, |
| | HOW THE GUY WIRE WILL BE SECURED AT EACH END, WHAT WILL |
| | THE GUY WIRE BE FASTENED TOO AND TYPE OF FASTENERS. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |