| Plan Review Notes For Permit 15060333 |
| Permit Number |
15060333 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-08-04 06:27:13 | 1) COMPLY WITH 2010 FBC-R R4101.6.3 FOR WATER VELOCITY. | | | 2) SUBMIT DETAILS FOR ENTRAPMENT PROTECTION. FBC-R | | | SEC.R4101.6.6. | | | 3) WATER SUPPLY SHALL COMPLY WITH 2010 FBC-R SEC. | | | R4101.9. | | | 4) COMPLY WITH 2010 FBC- R SEC.R4101.10.WHERE IS THE | | | POOL DISCHARGE/WASTE LINE? | | | 5) THE GENERAL CONTRACTOR SHALL ONLY CONSTRUCT THE POOL | | | SHELL PER F.S. 489.113 (3)(C). | | | 6) THE POOL PIPING PLAN SHOWS A "FLOOR DRAIN" BUT THERE | | | IS NO PIPING TO IT. CLARIFY. | | | 7) THE POOL RETURN IS SHOWN AS 2 INCH ON THE PLUMBING | | | SCHEDULE AND AS 1 1/2 INCH ON THE RETURN DETAIL. WHICH | | | IS IT? CLARIFY. | | | 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE MAIN | | | DRAIN COVER.THE COVER SHALL COMPLY WITH ASME/ANSI | | | A112.19.8 PER APSP 7 SEC.4.5. | | | 9) SUPPLY THE TOTAL DYNAMIC HEAD CALCULATIONS TO | | | DETERMINE THE MAXIMUM FLOW RATE OF THE PUMP.APSP 7 | | | SEC.4.4.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] |
|