| 2015-06-12 11:01:31 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 & NEC 2008 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE TWO SETS OF ELECTICAL PLANS FOR THE POOL | | | WITH THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. SPECIFY ALL CONDUIT AND WIRE SIZES ON | | | THE PLANS. FBC 107.2.1 | | | | | | 2) SHOW COMPLIANCE WITH NEC 680.26 FOR EQUIPOTENTIAL | | | BONDING. | | | | | | 3) SHOW COMPLIANCE WITH NEC 680.8 AND 680.10 FOR | | | OVERHEAD CONDUCTOR CLEARANCES AND UNDERGROUND WIRING | | | LOCATIONS. | | | | | | 4) SHOW COMPLIANCE WITH NEC 680.22 FOR AREA LIGHTING, | | | RECEPTACLES AND EQUIPMENT. | | | | | | 5) SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION | | | 403.9.2 TIME SWITCHES. | | | | | | | | | |
|